P83862 M Sheet 11 of 23
3.0 OPERATION
3.1 MODES OF OPERATION
The PS-12/24-8 POWERPATH can provide a 12 or 24VDC output when initiated by a 9 to 30VDC appliance (IN1 or IN2) or an
open contact (DRY1 or DRY2). The output will remain on until the deactivation of the input returns it to its normal mode.
The outputs can be configured as four Class “B” circuits, two Class “A” circuits, or two Class “B” and one Class “A” circuits.
Each Class "A" or Class "B" circuit is 2 Amps.
There are four output modes which can be used with either Class “A” or Class “B” circuits.
NORMAL MODE Used for a constant 12 or 24VDC output.
TEMPORAL MODE Provides a temporal output for appliances that can utilize a coded signal. (i.e. single
stroke bells and chimes and some horns) (NOTE: Do not use with Wheelock AS, NS,
RSS appliances.)
IN>OUT SYNC MODE Allows a coded signal or synchronization signal input to be utilized by the
POWERPATH. These appliances may come from a FACP, another PS-12/24-8 or a
Wheelock Synchronization Module (SM-12/24 or DSM-12/24). Audibles can also be
silenced.
WHEELOCK SYNC MODE Activates the built-in Wheelock Synchronization Mode for use with patented
synchronized horns and strobes. Audibles can also be silenced.
3.2 DIP SWITCH SETTINGS
The following is the DIP Switch settings for Output 1. Each of the remaining outputs is controlled similarly.
Figure 5:
Output DIP Switch(s)
1
2
3
4
ON
INPUT SELECT
TEMPORAL
STROBE SYNC
IN>OUT SYNC
OUT1-4
MODE DIP SWITCH SETTING
NORMAL MODE INPUT SELECT (4) “ON” for “IN1” or “DRY1”
“OFF” for “IN2” or “DRY2”
TEMPORAL (3) “OFF”
STROBE SYNC (2) “OFF”
IN>OUT SYNC (1) “OFF”
TEMPORAL INPUT SELECT (4) “ON” for “IN1” or “DRY1”
“OFF” for “IN2” or “DRY2”
TEMPORAL (3) “ON”
STROBE SYNC (2) “OFF”
IN>OUT SYNC (1) “OFF”
IN>OUT SYNC INPUT SELECT (4) “ON” for “IN1” or “DRY1”
“OFF” for “IN2” or “DRY2”
TEMPORAL (3) “OFF”
STROBE SYNC (2) “OFF”
IN>OUT SYNC (1) “ON”
WHEELOCK SYNC INPUT SELECT (4) “ON” for “IN1” or “DRY1”
“OFF” for “IN2” or “DRY2”
TEMPORAL (3) “OFF”
STROBE SYNC (2) “ON”
IN>OUT SYNC (1) “ON”