Installation and operating instructions Wilo-Control CC-Booster 21
*key: R = read-only; RW = read and write;
W = write only
40139
40140
(138 139)
Fault status BITMAP32 0: Sensor fault
1: Maximum
pressure
2: Minimum
pressure
4: Dry running
5: Pump 1 error
6: Pump 2 error
7: Pump 3 error
8: Pump 4 error
9: Pump 5 error
10: Pump 6 error
11: Pump 7 error
12: Pump 8 error
14: Battery
nearly empty
16: External
alarm
24: E43.0
External signal
R 31,000
40240
40241
(239 240)
Fault status 2 BITMAP32 R 31,000
40141
(140)
Acknowledge BOOL W 31,000
40159
(158)
System control BITMAP 0: Ext. Off
1: Pump cycling
2: Start pump
3: Stop pump
4: Constant
speed analogue
5: Constant
speed fieldbus
RW 31,000
40160
(159)
Control value
constant speed
UINT16 0.01 % R(W) 31,000
40247
(246)
FC type ENUM (CC-FC only) 0. FC202
1. VLT2800
2. VLT6000
R 31,000
40248
(247)
FC status BITMAP (CC-FC only) 0: Control OK
1: Drives OK
2: Interface OK
3: Warning
4: FC running
5: Voltage
warning
6: Current
warning
7: Temperature
warning
R 31,000
Holding
register
(Protocol)
Name Data type Scale & unit Elements Access* Added