Installation and operating instructions Wilo-Control CC-Booster 17
11 Appendix
11.1 ModBus: Data types
11.2 ModBus: Parameter overview
Data type Description
INT16 Integers in the range from -32768 to 32767.
The number range actually used for a data point may be different.
UINT16 Unsigned integers in the range from 0 to 65535.
The number range actually used for a data point may be different.
ENUM Is a list. Only one of the values listed in the parameters can be set.
BOOL A Boolean value is a parameter with exactly two states (0 false and 1 true). Generally, all values greater than
zero are classified as true.
BITMAP* Is an array of 16 Boolean values (bits). Values are indexed from 0 to 15. The number read from or written to the
register is the sum of all bits with the value 1 multiplied by 2 to the power of its index.
Bit 0: 2
0
= 1
Bit 1: 2
1
= 2
Bit 2: 2
2
= 4
Bit 3: 2
3
= 8
Bit 4: 2
4
= 16
Bit 5: 2
5
= 32
Bit 6: 2
6
= 64
Bit 7: 2
7
= 128
Bit 8: 2
8
= 256
Bit 9: 2
9
= 512
Bit 10: 2
10
= 1024
Bit 11: 2
11
= 2048
Bit 12: 2
12
= 4096
Bit 13: 2
13
= 8192
Bit 14: 2
14
= 16384
Bit 15: 2
15
= 32768
BITMAP32 Is an array of 32 Boolean values (bits). Please check Bitmap for the calculation details.
* Example for clarification:
Bit 3, 6, 8, 15 are 1; all others are 0. The sum is then 2
3
+2
6
+2
8
+2
15
= 8+64+256+32768 = 33096. It is also possible to do the
calculation the other way round. Based on the bit with the highest index, check whether the read number is greater than/equal
to the power of two. If this is the case, bit 1 is set and the power of two is deducted from the number. Then the check with the
bit with the next lower index and the recently calculated residual number is repeated until bit 0 is obtained or the residual num
-
ber is zero. Example for clarification: The read number is 1416. Bit 15 will be 0, since 1416 < 32768. Bits 14 to 11 will also be
0. Bit 10 will be 1, since 1416 > 1024. The remainder will be 1416-1024=392. Bit 9 will be 0, since 392 < 512. Bit 8 will be 1,
since 392 > 256. The remainder will be 392-256=136. Bit 7 will be 1, since 136 > 128. The remainder will be 136-128=8.
Bits 6 to 4 will be 0. Bit 3 will be 1, since 8 = 8. The remainder will be 0. The remaining bits 2 to 0 will thus all be 0.
Holding
register
(Protocol)
Name Data type Scale & unit Elements Access* Added
40001
(0)
Communication
profile version
UINT16 0.001 R 31,000
40002
(1)
Wink service BOOL RW 31,000
40003
(2)
Type of switch
-
gear
ENUM 3. CC
4. CC...FC
5. CCe
7. CCe NWB
R 31,000
40004
40005
(3 4)
Switchgear data
PLC version
UINT32 0.000001 R 31,000
40006
40007
(5 6)
Switchgear data
HMI version
UINT32 0.000001 R 31,000