English
18 WILO SE 12/2020
40008 –
40009
(7 – 8)
Switchgear data
ID
UINT32 1 R 31,000
40010 –
40011
(9 – 10)
Switchgear
circuit diagram
number
UINT32 1 R 31,000
40012
(11)
Switchgear data
month of
manufacture
UINT16 1 R 31,000
40013
(12)
Switchgear data
year of
manufacture
UINT16 1 R 31,000
40014
(13)
BusCommand
-
Timer
ENUM 0. -
1. Off
2. Set
3. Active
4. Reset
5. Manual
RW 31,000
40015
(14)
Drives on/off BOOL RW 31,000
40016
(15)
Pump speed
manual 1
UINT16 0.1 % (CCe only) RW 31,000
40017
(16)
Pump speed
manual 2
UINT16 0.1 % (CCe only) RW 31,000
40018
(17)
Pump speed
manual 3
UINT16 0.1 % (CCe only) RW 31,000
40019
(18)
Pump speed
manual 4
UINT16 0.1 % (CCe only) RW 31,000
40020
(19)
Pump speed
manual 5
UINT16 0.1 % (CCe only) RW 31,000
40021
(20)
Pump speed
manual 6
UINT16 0.1 % (CCe only) RW 31,000
40024
(23)
FC ON/OFF BOOL (CC-FC only) R 31,000
40025
(24)
Control mode ENUM 0. p-c R 31,000
40026
(25)
Actual value INT16 0.1 bar R 31,000
40027
(26)
Current setpoint INT16 0.1 bar RW
R (SCe NWB)
31,000
40028
(27)
Number of pumps UINT16 1 R 31,000
40030
(29)
Standby pump
ON/OFF
BOOL R 31,000
40032
(31)
Index base-load
pump
UINT16 1 R 31,000
40033
(32)
Pump status 1 BITMAP 0: Auto
1: Manu
2: Deactivated
3: Running
5: Fault
R 31,000
40034
(33)
Pump status 2 BITMAP 0: Auto
1: Manu
2: Deactivated
3: Running
5: Fault
R 31,000
40035
(34)
Pump status 3 BITMAP 0: Auto
1: Manu
2: Deactivated
3: Running
5: Fault
R 31,000
Holding
register
(Protocol)
Name Data type Scale & unit Elements Access* Added