Installation and operating instructions Wilo-Control CC-Booster 19
40036
(35)
Pump status 4 BITMAP 0: Auto
1: Manu
2: Deactivated
3: Running
5: Fault
R 31,000
40037
(36)
Pump status 5 BITMAP 0: Auto
1: Manu
2: Deactivated
3: Running
5: Fault
R 31,000
40038
(37)
Pump status 6 BITMAP 0: Auto
1: Manu
2: Deactivated
3: Running
5: Fault
R 31,000
40041
(40)
Pump mode 1 ENUM 0. Off
1. Manu
2. Auto
RW 31,000
40042
(41)
Pump mode 2 ENUM 0. Off
1. Manu
2. Auto
RW 31,000
40043
(42)
Pump mode 3 ENUM 0. Off
1. Manu
2. Auto
RW 31,000
40044
(43)
Pump mode 4 ENUM 0. Off
1. Manu
2. Auto
RW 31,000
40045
(44)
Pump mode 5 ENUM 0. Off
1. Manu
2. Auto
RW 31,000
40046
(45)
Pump mode 6 ENUM 0. Off
1. Manu
2. Auto
RW 31,000
40049
(48)
Pump operating
mode
ENUM 0. Cascade
1. Vario
R 31,000
40050
(49)
Current speed
pump 1
UINT16 0.1 % (CCe)
1 rpm (CC-FC)
R 31,000
40051
(50)
Current speed
pump 2
UINT16 0.1 % (CCe)
1 rpm (CC-FC)
R 31,000
40052
(51)
Current speed
pump 3
UINT16 0.1 % (CCe)
1 rpm (CC-FC)
R 31,000
40053
(52)
Current speed
pump 4
UINT16 0.1 % (CCe)
1 rpm (CC-FC)
R 31,000
40054
(53)
Current speed
pump 5
UINT16 0.1 % (CCe)
1 rpm (CC-FC)
R 31,000
40055
(54)
Current speed
pump 6
UINT16 0.1 % (CCe)
1 rpm (CC-FC)
R 31,000
40062
(61)
General status BITMAP 0: SBM
1: SSM
R 31,000
40068
(67)
Setpoint 1 UINT16 0.1 bar RW 31,000
40069
(68)
Setpoint 2 UINT16 0.1 bar RW 31,000
40070
(69)
Setpoint 3 UINT16 0.1 bar RW 31,000
40074
(73)
Application ENUM 0. Booster R 31,000
40075
(74)
External setpoint INT16 0.1 bar R 31,000
40076
(75)
Activate external
setpoint
BOOL RW 31,000
Holding
register
(Protocol)
Name Data type Scale & unit Elements Access* Added