Installation and operating instructions Wilo-Control CC-Booster 5
5Product information
5.1 Type key
5.3 Scope of delivery
CC-Booster switchgear
Circuit diagram
CC-Booster installation and operating
instructions
Frequency converter installation and operating
instructions (only for CC... FC version)
Factory test report
e.g.: Wilo-Control CC-B 3x10A T34 DOL FC WM
CC
CCe
Comfort Control switchgear for fixed
speed pumps
Comfort Control switchgear for electronic
pumps
Pressure boosting application
4 x Number of pumps 1 6
10 Max. rated current per pump in amperes
[A]
T Mains connection:
M = alternating current (1~)
T = three-phase current (3~)
34 Rated voltage:
2 = 220 230 V
34 = 380 400 V
DOL Pump activation type:
DOL = direct
SD = star-delta
FC With Frequency Converter
WM Installation type:
WM = Switchgear is mounted on a
mounting bracket (wall mounted)
BM = Floor model (base mounted)
5.2 Technical data
Mains supply voltage [V]: See rating plate
Frequency [Hz]:
50/60 Hz
Control voltage [V]:
24 VDC; 230 VAC
Max. current consumption [A]: See rating plate
Protection class:
IP54
Max. fuse protection on mains side [A]:
See circuit diagram
Ambient temperature [°C]:
0 to +40 °C
Electrical safety: Pollution degree II