EasyManua.ls Logo

Wilo Rexa UNI - Page 14

Wilo Rexa UNI
32 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
en Installation and electrical connection
14 WILO SE 2017-03
A dry run of the pump is prohibited! Avoid air pockets in
the hydraulics housing or in the pipe system. Ensure the
water level never falls below the minimum. The install-
ation of a dry-running protection is recommended!
6.4.1 Indications for double pump operation
If several pumps are used in an operating space, min-
imum distances between the pumps and the wall must
be complied with. Here there is a difference in the dis-
tances depending on the type of system: Alternating
operation or parallel operation.
d
A
2
A
1
Fig.3: Minimum distances
d Diameter hydraulics housing
A
1
Minimum distance from the wall:
- alternating operation: min. 0.3×d
- parallel operation: min. 1×d
A
2
Distance to discharge pipelines
- alternating operation: min. 1.5×d
- parallel operation: min. 2×d
6.4.2 Note on DN50/65 combination flange
The Rexa UNI V06... is equipped with a DN50/65 com-
bination flange. The nuts on the combination flange are
factory-set to the DN65 flange. For use with a DN50
flange, adjust the nuts at the flange. The flange can be
reset to DN65 at any time!
Fig.4: Adjust combination flange
No accessories mounted on flange.
Nut is freely accessible.
1. Push the nut inwards onto the small hole circle using a
screwdriver.
The flange connection is reset to DN50.
6.4.3 Maintenance tasks
After a storage period of more than 6months, check
the oil in the sealing chamber prior to installation:
1
Fig.5: Check the oil
1 Screw plug sealing chamber
Pump is not installed.
Pump is not connected to the mains.
Protective equipment has been put on!
1. Place the pump horizontally on a firm surface. The
screw plug points upwards. WARNING!Risk of hands
being crushed. Ensure that the pump cannot fall over
or slip away!
2. Unscrew the screw plug.
3. Place a suitable tank to collect the operating fluid.
4. Drain the operating fluid: Rotate the pump until the
opening points downwards.
5. Check the operating fluid:
If the operating fluid is clear, reuse operating fluid.
If the operating fluid is contaminated (black), fill
with new operating fluid. Dispose of operating
fluid in accordance with the local regulations!
Notify customer service if an operating fluid con-
tains metal chips!
6. Pour in operating fluid: Rotate the pump until the
opening points upwards. Fill-in the operating fluid into
the opening.
Comply with the specifications for operating fluid
locations and quantity! When recycling the operat-
ing fluid, check the quantity and if required adjust
it!

Related product manuals