42 WILO SE 06/2011
5.2.0.0 BMS Settings for Building Manage-
ment System (BMS) – building
automation
Incl. all sub-menus, only dis-
played when BMS is active
5.2.1.0
LON/CAN/IF-
Modul
Wink/service
The wink function permits the
identification of a device in the
BMS network. A "wink" is execu-
ted by confirmation.
Only displayed when LON,
CAN or IF-Module is active
5.2.2.0
Local/remote
operation
BMS local operation Temporary state, automatic
reset to remote operation
after 5 min
BMS remote operation
5.2.3.0 Bus address Setting of bus address
5.2.4.0 IF gateway val A Specific settings of the IF-
Module, depends on protocol
type
Further information can be
found in the installation and
operating instructions of the
IF-Modules
5.2.5.0
IF gateway val C Specific settings of the IF-
Module, depends on protocol
type
Further information can be
found in the installation and
operating instructions of the
IF-Modules
5.2.6.0
IF gateway val E Specific settings of the IF-
Module, depends on protocol
type
Further information can be
found in the installation and
operating instructions of the
IF-Modules
5.2.7.0
IF gateway val F Specific settings of the IF-
Module, depends on protocol
type
Further information can be
found in the installation and
operating instructions of the
IF-Modules
5.3.0.0
IN1 (sensor input) Settings for sensor input 1 Not displayed in the manual
control mode (incl. all sub-
menus)
5.3.1.0
IN1 (sensor value
range)
Display of sensor value range 1 Not displayed with PID con-
trol
5.3.2.0
IN1 (value range) Setting of the value range
Possible values: 0...10 V/2...10 V/
0...20 mA/4...20 mA
5.4.0.0 IN2 Setting for external setpoint
input 2
5.4.1.0 IN2 active/inactive ON
External setpoint input 2 active
OFF
External setpoint input 2 inac-
tive
5.4.2.0 IN2 (value range) Setting of the value range
Possible values: 0...10 V/
2...10 V/0...20 mA/4...20 mA
Not displayed when IN2 =
inactive
5.5.0.0
PID parameters Settings for PID control Only displayed when PID
control is active (incl. all sub-
menus)
No. Designation Type Symbol Values/explanations Display conditions
±
±
±
±
±
±
±
±
±
±