Installation and operating instructions Wilo-TOP-Z 29
English
rial (pump housing made from red brass) and design conformity with the rele-
vant regulations (TrinkwV., ACS, WRAS, W3d, guidelines for creating potable
water installations).
If pumps of the series Wilo-TOP-Z in EN-GJL (pump housing of grey cast iron)
are used in domestic hot water circulation systems, the national regulations and
guidelines should be complied with as necessary.
6.2 Terminal boxes
There are seven terminal boxes (Fig. 4) for all pump types, which are assigned,
as per table 1, to the pump types:
Table 1: Assignment of terminal box types to pump types (see also Fig. 4)
The fittings for the terminal boxes can be found in Table 2:
Table 2: Fitting of terminal boxes
1) The light indicator signals are carried by a common fibre optic cable to the cover, so that the signals are visible
from outside.
2) When mains voltage is present, the lamp lights up green.
• The direction of rotation signal lamp lights up green when mains voltage is pres-
ent and the direction of rotation is correct; if the direction of rotation is incor-
rect, the control lamp goes out (see the section “Commissioning”).
Mains max. power consumption P
1
Terminal box type
connection (see rating plate data) TOP-Z
1~ 95 W ≤ P
1
max ≤ 205 W 1/2
295 W ≤ P
1
max ≤ 345 W 3/4/5
3~ 95 W ≤ P
1
max ≤ 215 W 6
305 W ≤ P
1
max ≤ 1445 W 7
Terminal box Direction of rotation signal lamp Variable speed control
type (Fig. 4, item 1) (Fig. 4, item 3)
1 - Speed selection switch, 3-step
2 - Internal or external,
Bridging of contacts
“x1-x2” or “x1-x3” or “x1-x4”
3 - Speed selection switch, 3-step
4 - Internal or external,
Bridging of contacts
“x1-x2” or “x1-x3” or “x1-x4”
5 -
2)
Switching plug, 2-step
6 X (internal) Switching plug, 3-step
7 X
1)
Switching plug, 3-step