7 Installation and electrical connection
DANGER! Risk of fatal injury!
Incorrect installation and improper electrical connections can be life-
threatening. Danger from electrical current must be eliminated.
The installation and electrical connection may only be carried out by
qualified personnel in accordance with the applicable regulations!
Adhere to accident prevention regulations!
Comply with the regulations of the local energy supply company!
Pumps with pre-assembled cable:
Never pull on the pump cable.
Do not bend the cable.
Do not place objects on the cable.
7.1 Installation
WARNING! Risk of injury.
Incorrect installation can result in personal injury.
There is a crushing hazard.
There is a risk of injury due to sharp edges/burrs. Wear appropriate
protective clothing (e.g. safety gloves)!
There is a risk of injury caused by the pump/motor falling. Prevent the
pump/motor from falling, if required, by using suitable lifting gear.
CAUTION! Risk of material damage!
Incorrect installation can result in material damage.
Only use qualified personnel for installation work!
Observe national and regional regulations!
When the pump needs to be transported, it may be carried only by the
motor/pump housing. Not by the module/terminal box!
Installation within a building:
Install the pump in a dry, well-ventilated room. Ambient temperatures
below -20 °C are not permitted.
Installation outside a building (outdoor installation):
Install the pump in a chamber (e.g. light well, ring chamber) with cover or in
a cupboard/housing as weather protection. Ambient temperatures
below -20 °C are not permitted.
Avoid exposure of the pump to direct sunlight.
Protect the pump so that the condensation drain grooves remain free from
contaminants (Fig. 6).
Protect the pump against rain. Dripping water from above is permitted pro-
vided that the electrical connection has been established in accordance with
the installation and operating instructions and properly sealed.