Displaying / Modifying control parameters
The control parameters can only be modi ed or displayed via Wolf control accessories
with eBUS capability. For procedures, check the operating instructions of the relevant
accessories.
Modicationsmustonlythecarriedoutbyarecognisedheatingcontractor
orbytheWolfcustomerservice.
Incorrectoperationcanleadtosystemfaults.
Please note when adjusting parameterA09 (frost protection / outside
temperature), that frost protection is no longer safeguarded if you set
temperatureslowerthan 0°C.Thiscan resultindamage totheheating
systemandallitscomponents(e.g.pipes,radiators,etc.).
NB
NB
Parameter overview
(Settingsandfunctionsonthefollowingpages)
Parameter Setting range Factory setting
A09
Frostprotectionlevel -20to+10°C +2°C
A10
ParallelDHWoperation 0/1 0
A14
MaximumDHWtemperature 60to80°C 65°C
HG01
Burnerswitchingdifferential(dynamic) 5 to 30 K 15 K
HG06
Pumpoperatingmode 0/1/2 0
HG07
Boilercircuitpumprun-ontime 0to30min 3min
HG08
MaximumlimitboilercircuitTV-max 40to90°C 75°C
HG09
Burnercycleblock 1to30min 4min
HG13
ProgrammableinputE1 1 to 11 1
HG14
ProgrammableoutputA1 0 to 14 0
HG15
Cylinderhysteresis 1 to 30 K 5 K
HG19
Cylinderprimarypumprun-ontime 0to10min 3min
HG20
Max.cylinderheatingtime 0to5h 2h
HG21
MinimumboilerwatertemperatureTK-min.* 38to90°C 38°C
HG22
MaximumboilerwatertemperatureTK-max. 50to90°C 80°C
HG24
DHWsensoroperatingmode 1/2/3 1
HG25
BoilerexcesstemperatureduringDHWcylinder
heating
0 to 40 K 10 K
HG26
Boilersoftstart 0/1 1
HG32
Returntemperatureraising** 0to70°C 30°C
HG33
Hysteresistime 1to30min 10min
HG34
eBUSfeed 0/1/2 2
HG35
0-5Vinputfortelecontrolsystem 0/1 0
HG50
Testfunctions 1 to 5 -
HG70
Display
Multifunction
inputE1
-50sensorshortcircuitorcontactclosed
-60sensorleadbreakorcontactopen
ActualtemperatureheadersensorHG13=7
ActualtemperaturereturnsensorHG13=11
* setto50°Cforpressurejetgasburners
** setto40°Cforpressurejetgasburners