Parameter setup report
Wolfrecommendsyoucompletethesettingreportcarefullyandtokeepitsafetoenableaquick
solutiontobefoundduringserviceandincaseofafullreset.
Parameter Setting range Factory
setting
Individual
setting
A09
Frostprotectionlevel -20to+10°C +2°C
A10
ParallelDHWoperation 0/1 0
a14
MaximumDHWtemperature 60to80°C 65°C
HG01
Burnerswitchingdifferential
(dynamic)
5 to 30 K 15 K
HG06
Pumpoperatingmode 0/1/2 0
HG07
Run-ontime
Boilercircuitpump
0to30min 3min
HG08
Maximumlimit
BoilercircuitTV-max
40to90°C 75°C
HG09
Burnercycleblock 1to30min 4min
HG13
ProgrammableInputE1 1 to 11 1
HG14
ProgrammableOutputA1 0 to 14 0
HG15
Cylinderhysteresis 1 to 30K 5 K
HG19
Run-ontime
Cylinderprimarypump
0to10min 3min
HG20
Max.cylinderheatingtime 0to5h 2h
HG21
Minimumboilerwater*
temperatureTK-min.
38to90°C 38°C
HG22
Maximumboilerwatertemperature
TK-max.
50to90°C 80°C
HG24
DHWsensoroperatingmode 1/2/3 1
HG25
Excessboilertemperatureduring
cylinderheating
0 to 40 K 10 K
HG26
Boilersoftstart 0/1 1
HG32
Returntemperatureraising** 0to70°C 30°C
HG33
Hysteresistime 1to30min 10min
HG34
eBUSfeed 0/1/2 2
HG35
0-5Vinputfortelecontrolsystem 0/1 0
HG50
Testfunctions 1 to 5 -
HG70
Display
Multifunction
inputE1
-50sensorshortcircuitorcontactclosed
-60sensorleadbreakorcontactopen
ActualtemperatureheadersensorHG13=7
ActualtemperaturereturnsensorHG13=11
* setto50°Cforpressurejetgasburners
** setto40°Cforpressurejetgasburners