Wolf R1 - Contractor Level Parameters - Pump Operation; Pump Operating Mode (HG06)

Wolf R1
36 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3061809_121014
Feed pump for heating systems with cascade control and /
or low loss header
Heatingcircuitpumpbecomesthefeedpump.
Theheadersensoraffectstheheatingoperationaswellascylinder
heating.Thefeedpumprunsonlywhenthereisaburnerdemand.
Pumprun-oninaccordancewithparameterHG07.
Softstarting:AtTK
Ist
< TK
min
(38°C)feedpump"OFF".
MKP and cylinder primary pump continue to run with soft
starting.
Note: Increase the pump run-on time from 3 min to 15 min.
SettheparameterHG13to7.
Pump operating mode 1:
Pump operating mode 0:
Heating circuit pump for heating systems without cascade
control and without low loss header
Theheatingcircuitpumprunsconstantlywhenthere is a heat
demand.TheheatingcircuitpumpwillbeswitchedOFFduring
DHWheating,ifDHWpriorityhasbeenselected.
Pump operating mode
Parameter HG06
HG06
0
Factorysetting:0
Settingrange:0/1
Individual setting: ______
ZUP = Feedpump
SPL = Cylinderprimarypump
PLP = Bufferprimarypump
SF = Cylindersensor
SAF = Headersensor
MK1 = Mixercircuit
MKP= Mixercircuitpump
Oil/gasboiler
SAF
ZUP
MKP
MK1
SPL
Cylinder
Lowloss
header
orbuffer
cylinder
SF
Hydraulicscheme:
Contractor level parameters