Contractor level parameters
The control unit is equipped with a dynamic burner switching
differentialtooptimisetheselectedburnerswitchingdifferential
atvariousboilerloads.Thisfunctioncorrectstheselectedburner
switchingdifferential(parameterHG01)throughload-dependent
burnerruntimes.Theburnerswitchingdifferentialisreducedtoa
minimumvalueof5K,iftheburneroperatingtimeincreasesuptothe
selectedhysteresistime.Thismakestheselectedburnerswitching
differential effective at low boiler loads (rapid heat-up = short
burnerruntime).Thiseffectivelypreventsshortburnerruntimes
andcycling.Withlongerburnerruntimes(highheatdemand),the
switchingdifferentialwillbereducedto5K.Thispreventstheboiler
beingheatedtounnecessarilyhightemperatures.Thisoptimises
theenergyconsumptionoftheheatingsystem.
Thisfunctionpreventsshortburnerruntimesandfrequentcycling.
Thisprotectstheenvironmentandminimiseswear.
Hysteresis time
Parameter HG33
HG33
10
Factorysetting:10min
Settingrange:1to30min
Individual setting: ______
Ensurethereturntemperatureisraisedinheatingsystemswith
awatercontentgreaterthan20l/kWoutput.Forboilerswitha
pressure-jetoilburneroratmosphericgasburner,theminimum
return temperature is 30 °C, for boilers with pressure-jet gas
burner40°C.
Raising the return
temperature
Parameter HG32
HG32
30
Factorysetting:30
Settingrange:0to70°C
Individual setting: ______
Theoptionalboilersoftstartprotectstheboileragainstcorrosion
thatcanoccurwhen theboiler isheatedfromacoldstate,i.e.
throughcondensateseparationinthedewpointrange.Theboiler
circuitpumpwillbeswitchedOFF,iftheboilerwatertemperature
falls2KbelowthesetvalueTK-min.Thepumpwillbeenabled
whentheboilerwatertemperaturehasexceededtheminimum
limitTK-min.
TK-min.cannotbeachievedandtheheatingcircuitandcylinder
primary pumps remain OFF, if the burner is blocked through
external safety circuits (e.g. ue gas thermostat on solid fuel
boilers).
Boiler soft start
Parameter HG26
HG26
1
Factorysetting:1
Settingrange:0/1
Individual setting: ______