EGCP-1 Engine Generator Control Package Manual 26059
6 Woodward
Reactive (KVAR) Control
•
VAR sharing on isolated busses based on percentage reactive load (allows
different rated machines to proportionally balance KVAR loads).
•
Constant Power factor or VAR base loading on units which are in kW base
load control mode, or process control mode.
•
Externally adjustable VAR or PF control reference levels.
•
KVAR droop for manual VAR control.
Automatic Generator Sequencing
•
Automatically starts additional EGCP-1 equipped generators when load
exceeds a user specified percentage of the rated load of the operating
machines.
•
Provides controlled unloads for engines when the load is low enough that the
remaining engines will not exceed a user specified percentage of the rated
load.
•
Engine priority sequence can be changed from any unit or from a PC to
equalize run-time.
Generator Protective Features
•
Over/Under Voltage
•
Over/Under Frequency
•
Reverse Power (Inverse time delay)
•
Loss of Excitation
•
Overcurrent (Inverse time delay)
•
Loss of mains detection
•
Speed/Frequency Mismatch
•
Load Surge
Engine Protective Features
•
High/Low Coolant Temperature
•
High/Low Oil Pressure
•
Overspeed
•
Over Crank
•
Start Failure
PC Interface
•
Easy upload and download of configuration setpoints
•
A PC can control or monitor any unit at a site by a single connection to the
local operating network via RS-422 serial port using Modbus protocol.