Manual 26059 EGCP-1 Engine Generator Control Package
Woodward 137
LOWER LOAD
RATE
Min: 0.01
Max: 100.0
2.0 %/second
Item: Range: Default: As Set Value: Note:
FAST XFER
DELAY
Min: 0.1
Max: 30.0
0.1 second
Item: Range: Default: As Set Value: Note:
MAINS STABLE
DLY
Min: 1
Max: 30000
60 second
Item: Range: Default: As Set Value: Note:
GEN STABLE
DLY
Min: 1
Max: 30000
30 second
Item: Range: Default: As Set Value: Note:
LOAD HIGH LIMIT Min: 0.0
Max: 30000.0
30.0 kW
Item: Range: Default: As Set Value: Note:
HIGH LIMIT
ALARM
Disabled
Warning
Visual Alarm
Audible Alarm
Warning
Item: Range: Default: As Set Value: Note:
LOAD LOW LIMIT Min: 0.0
Max: 30000.0
5.0 kW
Item: Range: Default: As Set Value: Note:
LOW LIMIT
ALARM
Disabled
Warning
Visual Alarm
Audible Alarm
Disabled
Item: Range: Default: As Set Value: Note:
MAX GEN LOAD Min: 1
Max: 100
60 % system
load
Item: Range: Default: As Set Value: Note:
NEXT GENSET
DLY
Min: 1
Max: 1200
30 % system
load
Item: Range: Default: As Set Value: Note:
RATED LOAD
DELAY
Min: 1
Max: 1200
5 seconds
Item: Range: Default: As Set Value: Note:
MAX START TIME Min: 1
Max: 1200
30 seconds
Item: Range: Default: As Set Value: Note:
REDUCED LOAD
DLY
Min: 1
Max: 1200
30 seconds
Item: Range: Default: As Set Value: Note:
MIN GEN LOAD Min: 1
Max: 100
30 % system
load
Item: Range: Default: As Set Value: Note: