Caution: The Truecharge 20i/40i is NOT able to automatically
determine when to stop the equalization of a battery. The
battery specific gravity should be monitored throughout
equalization to determine the end of the equalize cycle.
Caution: Disconnect all loads connected to the battery during
equalization. The voltage applied to the battery during equal-
ization may be above safe levels for some loads.
Equalizing Your Batteries:
1) Follow the battery manufacturers instructions when equalizing
your flooded or wet batteries.
2) The equalization charging cycle is started by pressing the recessed
pushbutton switch marked "EQUALIZE" on the control panel.
Press and hold the pushbutton for about 5 seconds until both the
"CHARGING" and "READY" indicators light. The charger is
now in equalization mode.
3) Monitor the battery specific gravity during equalization with a
battery hydrometer. Equalization is complete when the specific
gravity of the battery remains constant for three hours. If equal-
ization is complete, terminate the equalization charge by momen-
tarily depressing the "EQUALIZE" pushbutton.