Chapter 3 Mechanical and Electrical Installation
14
When must be up and down , an air flow diverting plate should be fixed as shown in Fig.3-1 .
2) Installation space is shown in Fig.3-1 so as to ensure the heat dissipation space , but consider the
3) The installation bracket must be flame retardant .
4) In the applications where there are metal dusts , it is recommended to mount the heat sink outside
the cabinet . In this case , the space in the sealed cabinet should be large enough .
Fig.3-2 Remove the Plastic Lower Cover
heat dissipation of other components when placing the inverter .
3Install and Remove the Lower Cover
Lower Cover
Push out it forcibly
Heat sink should be taken into account during the mechanical installation . Due attention should be
paid to the following items :
1) Install the inverter vertically so that the heat may be expelled from the top , but do not install the
inverter upside down . If several inverters should be installed , they should be installed side by side .