V5 series inverter
37
P1.09 Max setting of CI P1.07 ~10.00V 0.01V 10.00V
P1.10 Frequency of the
max setting of CI
0.00~highest frequency 0.01Hz 50.00Hz
P1.11 Max input pulse
frequency of
PULSE
0.1~20.0K 0.1K 10.0K
P1.12 Min setting of
PULSE
0.0~P1.14
(Max setting of PULSE)
0.1K 0.1K
P1.13 Frequency of the
min setting of
PULSE
0.00~highest frequency 0.01Hz 0.00Hz
P1.14 Max setting of
PULSE
P1.12 (Min setting of PULSE) ~ P1.11
(Max input frequency)
0.1K 10.0K
P1.15 Frequency of the
max setting of
PULSE
0.00~highest frequency 0.01Hz 50.00Hz
P1.16 Input mode of CI 0: 4~20mA
1: 0~10V
- 0
3. Starting and Braking Prameters (Group P2)
Group P2: Starting and Braking Prameters
Parameter Name Range
Minmum
unit
Factory setting Change
P2.00 Starting mode 0: Start from the starting
frequency
1: Brake first and then start
from the starting frequency
2: detect current speed then
startup
1 0 ×
P2.01 Starting frequency 0.20~20.00Hz 0.01Hz 0.50Hz
P2.02 Holding time of starting
frequency
0.0~30.0s 0.1s 0.0s
P2.03 DC brake current when
startup
0.0~80.0% 0.1% 0%
P2.04 DC brake time when startup 0.0~60.0s 0.1s 0.0s
P2.05 Stopping mode
0: Decelerate
1: Free stop
2: Decelerate + DC brake
1 0 ×
P2.06 DC brake startup frequency
when stop
0.0~15.00Hz 0.0Hz 3.00Hz
P2.07 DC brake time when stop 0.0~60.0s 0.1s 0.0s
P2.08 DC brake current when stop 0.0~80.0% 0.1% 0.0%