V5 series inverter
46
P6.07 First 2 times fault records First 2 times fault records 1 0 *
P6.08 First 3 times fault records First 3 times fault records 1 0 *
P6.09 First 4 times fault records First 4 times fault records 1 0 *
P6.10 First 5 times fault records First 5 times fault records 1 0 *
P6.11 First 6 times fault records First 6 times fault records 1 0 *
8. Close-loop control parameters (Group P7)
Group P7: Close-loop control parameters
Parameter Name Range
Minmum
unit
Default
setting
Change
P7.00
Close-loop function selection
0: Disabled
1: Enabled
1 0 ×
P7.01 Channel selection 0: Digital input
1: VI (0~10V) analog voltage
2: CI analog
1 1
P7.02 Feedback channel selection 0: VI (0~10V) voltage input
1: CI analog input
2: VI+CI
3: VI-CI
4: Min{VI, CI}
5: Max {VI, CI}
1 1
P7.03 Appointetd channel filter 0.01~50.00s 0.01s 0.50s
P7.04 Feedback channel filter 0.01~50.00s 0.01s 0.50s
P7.05 Digital setting 0.00~10.00V 0.01V 0.00V
P7.06 Min setting value 0.0~Max P7.08 0.1 0.0
P7.07 Feedback value corresponding to
min setting value
0.0~100.0% 0.1 0.0
P7.08 Max setting value Min P7.06~100.0% 0.1 100.0
P7.09 Feedback value corresponding to
max setting value
0.0~100.0% 0.1 100.0
P7.10 Proportional KP 0.000~9.999 0.001 0.050
P7.11 Integral KI 0.001~9.999 0.001 0.050
P7.12 Sampling cycle T 0.01~10.00S 0.01 1.00
P7.13 Limits of deviation 0.0~20.0% 1 2.0
P7.14 Close loop adjustment characte-
ristic
0: Forward
1: Reverse
Note: relationship between setting value and speed
1 0 ×
P7.15 Integral adjustment selection
0: Stop integral adjustment when the frequency
reaches upper limit or lower limit
1: Continue the integral adjustment when the fre-
quency reaches high limit or lower limit
1 0 ×
P7.16 Close loop preset frequency 0~upper limit of of frequency 0.01Hz 0.00Hz
P7.17
Holding time of close-loop preset
frequency
0.0~250.0s
0.1s 0.1s ×
P7.18 Awakening threshold 0.00~500.00Hz 0.01Hz 0.01Hz ×
P7.19 backlash of zero-frequency 0.00~500.00Hz 0.01Hz 0.01Hz ×