ZG3 series 
13 
the output connection. 
  Output current 
Output current is 3A per point to drive resistance load for voltage below AC250V. 
Inductance load is below 80VA (AC100V or AC200V) and lamp load is below 100W (AC100V 
or AC200V). 
  Open leakage current 
There is no leakage current when output point is OFF, it can drive neon light. 
  Use life of relay output point 
The  standard  life  of  inductance  load  such  as  contactor,  solenoid  valve:  according  to  our 
experiment results, 20VA load is about 3 million times, 35VA load is about 1 million times, 
80VA load is about 0.2 million times. However, the life will extend if parallel connect surge 
absorber with the load.   
 
 
 
 
 
 
 
Note: T type (Y0, Y1) has no relay output, do not connect AC220V, or the product will be broken. 
 
 
 
 
◆  For DC inductance load, please parallel connect with commutate diode. If not connect with the 
commutate diode, the point’s life will be decreased greatly. Please choose the commutate diode 
which allow inverse voltage endurance up to 5~10 times of the load’s voltage, ordinal current 
exceeds load current.     
◆  Parallel connect AC inductance load with surge absorber can reduce noise and extend useful 
life of the points. 
 
 
+24V
circuit
drive
relay
Y*3
Y*2
Y*1
Y*0
M
5A~10A
Load
~
AC power
<AC250V
Relay output 
To avoid burning PLC basic circuit
set a fuse every 4 points
supply
Output circuit construction