Xtralis VESDA LCD Programmer Product Guide
www.xtralis.com 27
72. Relay Startup Mode - Displays the energize/de-energized condition for each relay.
If required, use the
+ - and press keys to change the energized/de-energized
state of relays.
ADM
73. Latching - This screen displays the latched/unlatched relay condition for different
levels of alarms in each sector, faults and scanning. In the latched condition the
reporting of an alarm or a fault continues to be reported even after the event is
over. Manual intervention is necessary to reset. If the condition is unlatched the
reporting of the condition automatically stops once the event is over. To latch an
alarm or a fault place a against the respective alarm level or fault. The isolate
function is fixed for unlatched and cannot be changed.
ADM
Scrn
No.
Description
Min.
Access
Level
Parameter Default
Relay Startup Mode
Relay 2 & 3 energized Energized
Relays 1, 4-7 (4-12) De-energized
Parameter Default
Latching
Sector (1-4) N/A
Fire 2 Latched
Fire 1 Latched
Alert Latched
Scanning N/A
Urgent Fault Latched
Minor Fault Latched
Isolate Unlatched