What to do if Xtralis Smoke Alarm filter is clogging?
- JjgreenSep 9, 2025
If the filter of your Xtralis Smoke Alarm is overdue for a change, change the filter immediately.
What to do if Xtralis Smoke Alarm filter is clogging?
If the filter of your Xtralis Smoke Alarm is overdue for a change, change the filter immediately.
Why has normalization failed in my Xtralis VESDA VLC-400 Smoke Alarm?
If there was an error during the Normalization process of your Xtralis Smoke Alarm, investigate whether there are differential pressures between the protected area and the detector that exceed 50Pa. Ensure that there are enough sampling holes – the minimum for standard configurations is 3 holes. Ensure the exhaust bung is removed. Introduce backventing if necessary.
How to troubleshoot an aspirator failure in Xtralis Smoke Alarm?
If the aspirator of your Xtralis Smoke Alarm has failed or is not functioning correctly, check the cable. If it is OK, contact your local Xtralis representative for a replacement aspirator.
Type | Aspirating Smoke Detector |
---|---|
Laser Class | Class 1 |
Number of Sampling Pipes | 4 |
Number of Sampling Points | Up to 40 |
Maximum Coverage Area | Up to 2000 m² |
Power Supply | 24 V DC |
IP Rating | IP30 |
Air Flow Monitoring | Yes |
Detection Principle | Laser Scattering |
Pipe Length | Up to 100 m |
Sensitivity Range | 0.005 to 20% obs/m |
Operating Temperature | 0°C to 39°C |
Operating Humidity | 10% to 95% RH (non-condensing) |
Relay Outputs | 3 |
Relay Contact Rating | 2 A @ 30 VDC |
Communication Interface | RS485 |
Covers loop isolation, power monitoring, AutoLearn, relay, remote LED, Apollo protocol, sensitivity modes, and delays.
Presents pre-engineered solutions and guidance on sampling pipe installation, including capillary sampling.
Details connecting air sampling pipe, power/signal cabling, Apollo loop wires, and setting DIP switches.
Step-by-step guide to normalizing airflow using Xtralis VSC for accurate airflow monitoring.
Explains how to start and use the AutoLearn function in Xtralis VSC to set optimal alarm thresholds.
Explains how to interrogate fault conditions via FACP or PC using Xtralis VSC.