4.2 Modes
4-23
J Passwords: A1-04, A1-05
D
Use constants A1-04 and A1-05 to write-protect the initialize-mode user constants.
D
User constants A1-01 through A1-03 and A2-01 through A2-32 can be displayed but not changed if
the contents of A1-04 and A1-05 are not the same.
D
To write-protect the initialize-mode user constants, set the password in A1-05 after inputting the de-
sired values in A1-01 through A1-03 and A2-01 through A2-32. User constant A1-05 can be displayed
by displaying A1-04 and pressing the Menu Key while pressing the Reset Key. (A1-05 can’t be dis-
played with the usual Key sequences.)
D
It will be possible to change the initialize-mode user constants again when the same password is writ-
ten to A1-04 and A1-05.
User
Change
during
Setting
Factory
Valid Access Levels
User
Constant
Number
Name
g
during
Opera-
tion
Setting
Range
Unit
Factory
Setting
V/f
Control
V/f with
PG
Open
Loop
Vector
Flux
Vector
A1-04
Password 1
×
0 to 9999 0
Q Q Q Q
A1-05
Password 2
×
0 to 9999 0
Q Q Q Q
A
EXAMPLE
"
Setting the Password to 1000
Use the following procedure to set the password to 1000.
Step Key Sequence Digital Operator Display Remarks
1
MENU
G5: Main Menu :
Operation
2
G5: Main Menu :
Initialize
3s
DATA
ENTER
Select Language
English
4
Press 4 times.
Enter Password
A104 = 0
5
Hold RESET.
RESET
And press MENU.
MENU
Select Password
A105 = 0
6
DATA
ENTER
Select Password
0000
The first digit will blink. The blinking
digit can be changed.
7
Select Password
1000
The value of the digit will increment
each time the Increment Key is
pressed and then stop at 9. Press the
Decrement Key to decrease the value.
8
DATA
ENTER
Entry Accepted
Writes-in the new setting.
Select Password
A105 = 1000
After a few seconds, the Operator dis-
play is as shown on the left.
9
ESC
Enter Password
A104 = 0
The password has been set to 1000.
To enable changing user constants, set the same password in A1-05 = 0.
J Setting User Constants: A2-01 to A2-32
D
User constants A2-01 through A2-32 specify the constants that can be displayed and changed when
the access level (A1-01) is set to 1 (user programs).
D
User constants A2-01 through A2-32 can be changed only in the Advanced access level and cannot
be changed during operation.
D
The following restrictions apply to setting/displaying user constants when the access level is set to the
user program access level.
Operation
The Quick-start level user constants can be displayed.
Initialize
The Quick-start level user constants can be displayed or set.
4

Table of Contents