MAIN
CIRCUIT
CAUTION
The
external
interconnection
wiring
must
be
performed
with
fol-
lowing
procedures
.
After
completing
VS-616G=1
interconnections,
be
sure
to
check
that
connections
are
correct
.
Never
use
control
circuit
buzzer
check
.
MAIN
CIRCUIT
INPUT/OUTPUT
(1)
Phase
rotation
of
input
terminals
L
1
(R),
L2
(S),
L3
(T)
has
no
effect
on
motor
rotation
.
(2)
To
reverse
motor
rotation,
interchange
any
two
of
the
motor
leads
.
(3)
Never
connect
the
AC
main
circuit
power
supply
to
output terminals
T
1
(U),
T2
(V),
or
T3 (W)
.
Inverter
damage
may
occur
.
(4)
Care
should
be
taken
to
prevent
contact
of wiring
leads
with
VS-616G3
cabinet, for
short-circuit
may
result
.
(5)
Never
connect
power
factor
correction
capacitors
to
VS-616G3
output
.
(6)
Never
open
or
close
contactors
in
the
output
circuit
unless
the
invert-
er
is
properly
sized
.
GROUNDING
Ground
the
casing of
the
VS-616G3
using
ground
terminal
G
(E)
.
(1)
Ground
resistance
should
be
11000
or
less
.
(2)
Never
ground
the
VS-616G3
in
common
with
welding
machines,
mo-
tors,
and
other
large-current
electrical
equipment
.
Run
the
ground
lead
in
a
separate
conduit
from
leads
of
large-current
electrical
equipment
.
(3)
Use
ground
leads
which
comply
with
AWG
standards
using
the
short-
est
length
possible
.
(4)
When
several
VS-616G3
units
are
used
side
by
side,
all
the
units
should
preferably
be grounded
directly
to
the
ground
poles
.
However,
con-
necting
the
ground
terminal
of
VS-616G3
units
in
parallel,
and
ground
ing only
one
of
the
VS-616G3
units
to
the
ground
pole
is
also
permissible (Fig
.
3)
.
However,
do
not
form
a loop
with
the
ground
leads
.
CORRECT
CORRECT
NOT
ACCEPTABLE
(a)
(b)
(C)
Fig
.
3
Grounding
of
Three
VS-616G3
Units
_
~
1,~G
UG