Notes:1Use1:1withaninveter.DonotconnectmorethanoneinvertertooneVS-656RC5.
2UsetheVS-656RC5whosecapacityisequaltooneexceedingtheinvertercapacitytobecombined.
3MakesuretousethespecifiedACreactor,fuse,andfuseholder.
4Donotusethisunitwithsingle-phasepowersupply.Usethree-phasepowersupply.
5Whenthepowersupplyisagenerator,checkthecapacityofthegenerator.ContactyourYASKAWArepresentative.
*UsetheVS-656RC5withlargeroutputcapacityiftheimbalanceratebetweenphasesexceeds2%.
Imbalanceratebetweenphasescanbecalculatedusingthefollowingformula(ConformingtoIEC1800-3).
Imbalanceratebetweenphases[%]= ×67
Max.voltage−Min.voltage
Three-phaseaveragevoltage
Model CIMR
−
R5A 23P7
3.7
13
10
25P5
5.5
19
15
27P5
7.5
26
20
2011
11
37
30
2015
15
51
40
2018
18.5
64
50
2022
22
77
60
2030
30
102
80
2037
37
126
100
RatedCapacity
RatedDCCurrent
RatedCurrentonPowerSide
RegenerativeTorque
VoltageFrequency
AllowableVoltageFluctuation
AllowableFrequencyFluctuation
ImbalanceRatebetweenPhases
200to220VAC50Hz,200to230VAC60Hz
−15to+10%
±3Hz/300ms(Freephaserotation)
Within2%
*
150%for30sec.100%for1min.,25%ED,80%continuous
kW
A
A
200VClass
Rating
InputPower
Supply
Rating
InputPower
Supply
Model CIMR
−
R5A 43P7
3.7
6
5
45P5
5.5
9
7.5
47P5
7.5
13
10
4011
11
19
15
4015
15
26
20
4018
18.5
32
25
4022
22
37
30
4030
30
51
40
4037
37
64
50
4045
45
77
60
4055
55
96
75
4075
75
128
100
RatedCapacity
RatedDCCurrent
RatedCurrentonPowerSide
RegenerativeTorque
VoltageFrequency
AllowableVoltageFluctuation
AllowableFrequencyFluctuation
ImbalanceRatebetweenPhases
380to460VAC50/60Hz
−15to+10%
±3Hz/300ms(Freephaserotation)
Within2%
*
150%for30sec.100%for1min.,25%ED,80%continuous
kW
A
A
400VClass
ControlMethod
InputPowerFactor
OverloadCapacity
OperationInput
1CContactOutput
PhotocouplerOutput
AnalogOutput
InstantaneousOvercurrent
BlownFuse
Overload
Undervoltage(DCVoltage)
Undervoltage(PowerSideVoltage)
Overvoltage(DCVoltage)
FinOverheat
PowerSupplyOpenPhase
PowerFrequencyError
PowerChargeIndication
Location
AmbientTemperature
Humidity
Vibration
120°currentconduction
0.9ormore(Ratedcurrent)
30sec.atapprox.150%ofratedcurrent.
Externalterminals4points(MANUALRUN,AUTORUN,EXFLT,RESET)
Fault(FAULT)
Photocoupleroutput2points(CONVREADY,RUN)
Analogoutput:1pointcanbereleased(Factorysetting:currentmonitor)
Stopsatapprox,200%ofthecurrentonpowerside
Motorstopsbyblownfuse.
Stopsafter30sec.at150%ofratedcurrent
200Vclass:stopsatapprox.190VDCorless400Vclass:stopsatapprox.380VDCorless.
200Vclass:stopsatapprox.150VACorless400Vclass:stopsatapprox.300VACorless.
200Vclass:stopsatapprox.406VDCormore400Vclass:stopsatapprox.812VDCormore.
Protectedbythermister
Stopsatpowersupplyopenphasedetection.
Stopsbyfluctuationmorethan±3Hzofratedinputfrequency.
Indicateduntilmainoutputvoltageisapprox.50Vorless.
Indoor(Protectedfromcorrosivegasesanddust)
-10to+40℃(Closedwall-mounted)-10to+45℃(Openchassistype)
90%RHorless(non-condensing)
Upto9.8m/s
2
(1G)lessthan20Hz,upto1.96m/s
2
(0.2G)at20to50Hz
Commonto200V/400VClass
Control
Characteristics
Status
Output
ProtectiveFunction
Environmental
Conditions