109
Protective
Operation
Output is shut
OFF and motor
coasts to a
stop.
EF!
(External fault)
Inverter receives an external
fault input from control circuit
terminal.
EF0: External fault reference
through MEMOBUS
communications
EF2: External fault input
command from control
circuit terminal S2
EF3: External fault input
command from control
circuit terminal S3
EF4: External fault input
command from control
circuit terminal S4
EF5: External fault input
command from control
circuit terminal S5
Check the external
circuit (sequence).
CPF-00
Initial memory fault is
detected.
Cycle power.
If the fault remains,
replace the digital
operator or inverter.
CPF-01
ROM error is detected.
Cycle power. If the fault
remains, replace the
digital operator or
inverter.
CPF-04
EEPROM fault of inverter
control circuit is detected.
Record all parameter
data and initialize the
parameters. (Refer
to page 25 for
parameter
initialization)
Cycle power.
If the fault remains,
replace the inverter.
Alarm Display