EasyManua.ls Logo

YASKAWA VS MINI J7 - Page 20

YASKAWA VS MINI J7
118 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
20
Other Functions
Display
Status Indicator LED RUN and ALARM provided as standard LEDs
Digital Operator
Available to monitor frequency reference, output
frequency, output current. 3 character, 7 segment
LED display.
Terminals
Main circuit: screw terminals
Control circuit: plug-in screw terminal
Wiring Distance between
Inverter and Motor
328ft (100m) or less†
Enclosure Open chassis or enclosed wall-mounted
Cooling Method
Cooling fan is provided for 200V, 0.75kW (3-/single
phase), 200V, 0.75kW (1.5HP), others are self-
cooling
Environmental
Conditions
Ambient Temperature
Open chassis: -10 to +50°C (14 to 122°F)
(not frozen)
Humidity 95% RH or less (non-condensing)
Storage Temperature* -20 to 60°F (-4 to +140°C)
Location Indoor (free from corrosive gases or dust)
Elevation 3280ft (1000m) or less
Vibration
Up to 9.8m / S
2
(1G) at less than 20Hz, up to 2m / S
2
(0.2G) at less than 20 to 50Hz
* Temperature during shipping (for short period)
† If the wiring distance between inverter and motor is long, reduce the inverter carrier
frequency.
For details, refer to “Reducing motor noise or leakage current (n46)” on page 79.
Voltage Class 400V 3-phase
Model
CIMR-J7A!!!!
3-phase 40P2 40P4 40P7 41P5 42P2 43P7