22
Terminal Description
* DC power supply input terminal is not available on CE/UL standards.
Type Terminal Name Function (Signal Level)
Main Circuit
R/L1,
S/L2,
T/L3
AC power supply input
Use main circuit power input (for single-phase inverter,
R/L1, S/L2).
Even thought T/L3 is available, do not use the terminal
for other purposes such as relay terminal.
U/T1,
V/T2,
W/T3
Inverter output Inverter output
+2, +1 DC reactor connection
When connecting optional DC reactor, remove the main
circuit short-circuit bar between +2 and +1.
+1, (–) DC power supply input
DC power supply input (+1: positive, –: negative)
*
Grounding
Grounding 200V: grounding to 100Ω or less
400V: grounding to 10Ω or less
Control Circuit
Input
Sequence
S1
Forward run input
Closed: FWD run
Photo-
coupler
insulation
24VDC,
8mA.
S2
Multi-function input selection 2
Factory setting closed: REV run
S3
Multi-function input selection 3
Factory setting: Fault reset
S4
Multi-function input selection 4
Factory setting: External fault (N.O.
contact)
S5
Multi-function input selection 5
Factory setting: Multi-step speed
reference 1
SC
Multi-function input selection common
Control signal common
Frequency
reference
FS Power for frequency setting +12V (permissible current 20mA max.)
FR
Master speed frequency reference
0 to +10DC (20kΩ) or 4 to 20mA (250Ω) or 20mA (250Ω) (1/1000 resolution)
FC
Frequency reference common
0V
Output
Multi-function
contact output
MA NO contact output
Form C contact
Factory setting: running
Contact capability
250VAC 1A or less,
30VDC 1A or less
MB NC contact output
MC Contact output common
AM Analog monitor output
Factory setting:
Output frequency 0 to +10VDC
0 to+10VDC, 2mA or
less,
8-bit resolution
AC Analog monitor common 0V