25
Parameters List
First Functions (Parameters n001 to n049)
No.
Register
No. for
Trans-
mission
Name Description
Initial
Setting
*User
Setting
Ref.
Page
01 0101H
Parameter write-in
prohibit / initialize
0: Parameter n001 set / read and
parameter n02 ~ n79 can be read.
(FREF of the operator can be set.)
1: Functions (parameters n01 ~ n79)
can be set / read.
6: Clear fault history
8: 2 wire initialize
(Japanese Specification)
9: 3 wire initialize
(Japanese Specification)
10: 2 wire initialize
(American Specification)
11: 3 wire initialize
(American Specification)
157
02 0102H
Operation reference
selection
0: Operator
1: Control circuit terminal
2: Communication
162
03 0103H
Frequency reference
selection
0: Volume
1: Frequency reference 1 (n21)
2: Control circuit terminal
(voltage 0 ~ 10V)
3: Control circuit terminal
(current 4 - 20 mA)
4: Control circuit terminal
(current 0 - 20 mA)
5: Not used (setting error)
6: Communication
(register number 0002H)
263
04 0104H
Stopping method
selection
0: Decel to stop
1: Coast to stop
082
05 0105H REV run prohibit
0: Reverse run enabled
1: Reverser run disabled
065
06 0106H
Operation stop key
selection
0: Stop key enabled
1: Stop key is enabled only when run
command is selected to the operator.
081
07 0107H
Frequency reference
selection
in local mode
0: Volume
1: Frequency reference selection (n21)
0 (Note4) 63
08 0108H
Setting method selection
for frequency reference
0: Frequency reference setting by the
operator is enabled with the ENTER
key input
1: Frequency reference setting by the
operator is not required the ENTER
key input.
063