43
Recommended Peripheral Devices
It is recommended that the following periheral devices be mounted between the AC
main circuit power supply and VS mini J7 input terminals R/L1, S/L2, and T/L3.
MCCB (Molded-case circuit breaker):
A circuit breaker should be connected for wiring protection.
Magnetic contactor:
Mount a surge suppressor on the coil (refer to the table shown below).
To assure optimum inverter life when using a magnetic contactor to start and stop
the inverter, do not exceed one stop per hour.
Recommended MCCB and magnetic contactor
200V 3-Phase
200V single-Phase
400V 3-Phase
VS mini J7 model J7 * *
20P1
J7 * *
20P2
J7 * *
20P4
J7 * *
20P7
J7 * *
21P5
J7 * *
22P2
J7 * *
23P7
Capacity (kVA) 0.3 0.6 1.1 1.9 3.0 4.2 6.7
Rated Output Current (A) 0.8 1.6 3 5 8 11 17.5
MCCB type NF30
(MITSUBISHI)
5A 5A 5A 10A 20A 20A 30A
Magnetic contactor type HI
(YASKAWA CONTROL)
HI-7E HI-7E HI-7E HI-7E HI-10-2E HI-10-2E HI-20E
VS mini J7 model
J7 * *
B0P1
J7 * *
B0P2
J7 * *
B0P4
J7 * *
B0P7
J7 * *
B1P5
Capacity (kVA) 0.3 0.6 1.1 1.9 3.0
Rated Output Current (A) 0.8 1.6 3 5 8
MCCB type NF30, NF50
(MITSUBISHI)
5A 5A 10A 20A 20A
Magnetic contactor type HI
(YASKAWA CONTROL)
HI-7E HI-7E HI-7E HI-10-2E HI-15E
VS mini J7 model
J7 * *
40P1
J7 * *
40P2
J7**
40P4
J7 * *
41P5
J7 * *
42P2
J7 * *
43P7
Capacity (kVA) 0.9 1.4 2.6 3.7 4.2 7.0
Rated Output Current (A) 1.2 1.8 3.4 4.8 5.5 9.2
MCCB type NF30, NF50
(MITSUBISHI)
5A 5A 5A 10A 10A 20A
Magnetic contactor type HI
(YASKAWA CONTROL)
HI-7E HI-7E HI-7E HI-10-2E HI-10-2E HI-10-2E