EasyManua.ls Logo

YASKAWA VS MINI J7 - Selecting Run;Stop Commands

YASKAWA VS MINI J7
118 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
62
Selecting Run/Stop Commands
Refer to page 63 to select either the LOCAL mode or REMOTE mode.
Operation method (RUN / STOP commands, FWD / REV run commands) can be
selected by the following method.
LOCAL Mode
When Lo (local mode) is displayed on the digital operator (when is
illuminated), or when the LOCAL / REMOTE changeover function is set as a
multi-function input and the input terminal is turned ON, run operation is enabled
by the or of the digital operator. FWD/REV is selected by
illuminating and using or key to select FWD or REV.
REMOTE mode
Select remote mode
The following two methods are used to select remote mode:
1. Select rE (remote mode) for selection.
2. When the local / remote switching function is selected as multi-function
input selection, turn OFF the input terminal to select remote mode.
Select operation method by setting the parameter n02.
n02=0: Enables the digital operator (same with local mode)
=1: Enables the multi-function input terminal (see fig. below)
=2: Enables communications (refer to page 96)
Example for using the multi-function input terminal as operation reference
(two-wire sequence) follows. For 3-wire sequencing, refer to page 85.
Operating (RUN /STOP commands) by communications
(When option card is installed)
Setting parameter n02 to 2 in REMOTE mode can give RUN / STOP commands by
communication (MEMOBUS). For details, refer to page 96.