Selecting Cooling Fan Operation
In order to increase fan life, the cooling fan can be set to operate when inverter is
running or when power is supplied.
Using MEMOBUS (MODBUS) Communications
Serial transmission is available with VS mini J7 using programmable controller
(MEMOCON series) and MEMOBUS. In order to perform serial communications, RS-
485/422 interface card (optional) must be installed.
MEMOBUS (MODBUS) communications
MEMOBUS system is composed of a single master (PLC) and slaves (1 to 31
VS-mini units).
Transmission between master and slave (serial communication) is controlled
according to the master program with the master initiating communication and the
slave responding.
The master sends a signal to one slave at a time. Each slave has a pre-registered
address No., and the master specifies the number and conducts signal
communication. The slave receives the transmission to carry out designated
functions and reply to the master.
n35 = 0 (factory setting) : Operates only when inverter is running.
(Continues operation for 1 minute after
inverter is stopped.)
= 1 : Operates while power is ON.