3
STANDARD SPECIFICATIONS
SPECIFICATIONS
English (Metric)
CH-MG150
CH-MG200
Capacity
Cooling
MBTU/hr (kW/hr)
2,400 (703.4)
Heating
MBTU/hr (kW/hr)
1,660 (486.5)
Chilled/Hot
Water
Chilled Water
Temperature
Inlet
°F (°C)
53.6 (12)
Outlet
°F (°C)
44.6 (7)
Hot Water
Temperature
Inlet
°F (°C)
132.8 (56)
Outlet
°F (°C)
140.0 (60)
Evaporator Pressure Loss
PSI (kPa)
9.2 (63.4)
Maximum Operating Pressure
PSI (kPa)
113.9 (785)
Rated Water Flow
GPM (l/s)
532.6 (33.6)
Water Retention Volume
Gal (liters)
69 (261.2)
Cooling
Water
Heat Rejection
MBTU/hr (kW/hr)
4,060 (1189.9)
Cooling Water
Temperature
Inlet
°F (°C)
85.1 (29.5)
Outlet
°F (°C)
94.3 (34.6)
Abs/Cond Pressure Loss
PSI (kPa)
7.2 (49.6)
Maximum Operating Pressure
PSI (kPa)
113.9 (785)
Rated Water Flow
GPM (l/s)
878.1 (55.4)
Water Retention Volume
Gal (liters)
153 (579.2)
Fuel
Type of Fuel
Natural Gas
Consumption
MBTU/hr (kW/hr)
2,000 (586.1)
Electrical
Power Source
208v or 230v / 60Hz / 3-phase
Consumption
kW
3.3
Minimum Circuit Amps
Amps
29.0
Maximum Overcurrent Protection
Amps
35
Capacity
Control
Cooling
30-100% Proportional
Heating
30-100% Proportional
Combustion
Burner Type
Low NOx Forced Draft (Proportional)
Flame Detection
Flame Rod
Ignition Type
Pilot w/ Intermittent Spark
Sound
dB(A)
74
Dimension
Width
Inches (mm)
80.9 (2057)
Depth
Inches (mm)
147.0 (3735)
Height (without vent cap)
Inches (mm)
97.6 (2480)
Height (including vent cap)
Inches (mm)
118.1 (3000)
Piping
Chilled/Hot Water
Inches
5 (Flange)
Cooling Water
Inches
6 (Flange)
Gas Piping
Inches
2 NPT
Weight
Dry
lbs (kg)
14,330 (6500)
Operating
lbs (kg)
16,183 (7340)
Note: All metric values are calculated from the Imperial values and are only approximate values.
1. Fuel Input is based on the high heat value of gas. Burner efficiency = 83%. Allowable supply gas pressure is 7”-10.5” wc.
2. Power consumption does not include external pumps or cooling tower fan motors.
3. “Width” dimension does not include Junction Box.
4. Specifications are all based upon water in all fluid circuits and fouling factor of 0.0005 ft²-hr-°F/Btu.
5. Pressure Loss ratings are +/- 10%.
6. Minimum Cooling Water flow is 100%.
Table 1 Specifications