1-43
IM 04L42B01-01E
Overview of Functions
1
Miscellaneous
• LimitationsontheCombinationsofEventsandActions
The combinations that are checked in the table below can be used.
Alarm ACK
Reset the relative timer
Load the settings
Adjust the time
Reset the alarm display
Remote
Event
Action
Output
Relay
Internal
Switch
Timer Match
Time
Timer
Alarm User
Key
Event
Edge
Switch
Event
Level
Switch
• LevelandEdge
The combinations of events and actions are summarized in the figure below.
Level
Level
State 1
State 2 Operation
Operation
executed
Edge Edge
Edge
Event
Action
OFF event
Level
Edge
Edge
EventActionExample
The following is an example for when the event is Internal switch (Level or Edge) and
the action is Memory start/stop (Level) or Manual sample (Edge).
Event Action
OFF
ON
OFF
Memory start
Memory stop ExecutionExecution
EdgeLevel
Event
(internal switch)
Switch
Action
Manual sample
Switch-Off
ON
LevelandEdgeoftheRemoteControlInputSignal
ON
OFF
For contact inputs, the remote signal rises when the contact switches from open to
closed and falls when the contact switches from closed to open. For open collector
signals, the remote signal rises when the collector signal (voltage level of the remote
terminal) goes from high to low and falls when the collector signal goes low to high.
You can reverse the above operations (see section 7.3 for details).