<6. In-process operation>
6-3
IM 12A01A02-71E 3rd Edition : Mar. 23, 2018-00
Alarms displayed by DEVICE_STATUS_1 to DEVICE_STATUS_8 resource block parameters
in their default setting are categorized as described in “NAMUR NE-107 Alarm Categories”
in the DEVICE_STATUS table in section 8.1. When an alarm occurs, a character string that
corresponds to an alarm category is assigned to FD_*_ACTIVE (index 1067 to 1070) [* indicates
FAIL, OFF SPEC, MAINT or CHECK]. (For example, an F category alarm is assigned to FD_
FAIL_ACTIVE) Similarly, procedures for processing alarms are assigned to FD_RECOMMEN_
ACT. For details on alarm displays and how to deal with them, refer to Table 6.2.
TheDTM-based“FieldDiagnostics”functiononFieldMateR2.06orlatermakescongurationor
checkingofalarmclassiedonNE-107easier.
For the detailed usage of “Field Diagnostics” function, refer to FieldMate user’s manual: IM
01R01A15-01EN.
Table 6.2 Field Diagnostic Alert
bit Indication of FD_*_ACTIVE
Indication of FD_RECOMMEN_ACT
Solution
32 Electronics failure Repair electronics Replaceelectricalpartse.g.amplier.
Orcontactsaleso󰀩ceorservicecenter.
31 Sensor/Actuator failure Repair Sensor/Actuator Replace mechanics e.g. sensor or
actuator.Orcontactsaleso󰀩ceor
service center.
30 Potential failure Investigate failure
Performreconguration,cleaning,wiring/
connector or electrical board check.
Ifalarmstillpersists,contactsaleso󰀩ce
or service center.
27 Backup function in operation Repair primary side Repair primary sensor before backup
sensor fails.
25 Firmware update error Retryupdatingrmware Retryrmwareupdate.Checkcauseof
the failure if alarm persists.
24 Communicationconguration
error
Congurecommunication
correctly
Correctcongurationofcommunication.
23 Non-operating-state Wait for a while Wait for a while. Check cause of the
failure if alarm persists.
22 Calibration warning Check calibration Investigate cause of failure and
recalibrate device.
21 Devicecongurationerror Conguredevicecorrectly Correctcongurationrelatingtosensor
or actuator.
20 Function restricted Conrmthestate Check if this is right state.
19 Simulation mode Conrmthestate Check if this is right state.
18 Manual mode Conrmthestate Check if this is right state.
17 Function Block notice Check Function Block status Check conditions of function
blocks. In order to avoid alarm from
unusedfunctionblocks,congure
RESOURCE2.FD_EXTENDC_MAP_n
(n: 1 to 3) parameter.
14 Sensor/Actuator out of range Checkspecication Checkspecicationofsensorand
actuator. Or process conditions may be
temporarily non-conforming.
13 Out of operating limit Check environment Checkenvironmentspecication
of sensor and actuator. Or process
environment may be temporarily non-
conforming.
10 Temporal decrease of value
quality
Check process or peripherals Check process and peripherals
conditions.
9 Deterioration estimated by
Time Based Maintenance
Check deterioration Check if maintenance is required.
8 Deterioration estimated by
Condition Based Maintenance
Check deterioration Check if maintenance is required.
4 Optional function
congurationerror
Checkoptionalconguration Checkcongurationofoptional
functions.
3 Alarm related information Conrminformation Check the alarm related information.
2 Process alarm Check process Check process conditions.
1 CHECK CHECK Check mode for the Sensor transducer
block is AUTO.