<2. WIRING AND INSTALLATION>
2-13
IM 12A01F01-02EN 2nd Edition : Feb. 19, 2019-00
2.5.4 Wiring IO module
First complete the sensor wiring. (Read 2.6)
Wire for mA input, mA output, contact input. Wiring for mA input may not be necessary according
to the specication.
n Wiring mA output
FLXA402 transmits 4-20 mA analog signals with maximum load of 600 Ω to peripherals including
a control system or recorders. IO module has mA output function.
Be sure to use shielded cables for output signal cables, and connect shield to terminal 63 (or
89*).
*: When mA I/O is “-A4”, the terminal 89 is used for mA input and cannot be used for output.
Use cables of rating 30 V AC or greater.
For wiring, use shielded multi-core cables.
Screws for IO module are all M3 with washers.
Terminal
number
Contact
terminals
Description
61 mA1+ 4-20 mA output 1+(with HART)
62 mA1- 4-20 mA output 1-
65 mA2+ 4-20 mA output 2+
66 mA2- 4-20 mA output 2-
81 mA3+ 4-20 mA output 3+ *1
82 mA3- 4-20 mA output 3- *1
85 mA4+ 4-20 mA output 4+ *1
86 mA4- 4-20 mA output 4- *1
63 SHILD Shield
89 SHILD Shield
*1 only when mA output is -A4 in the Sux Codes.
Figure 2.13 IO module terminal assignment