27
IM 12D06D05-01E
5
MENU STRUCTURECOMMISSIONING
Menu Parameter Default Range
values min. max.
AlarmS1 Setpoint 900.0mS/cm(high) -inf +inf
AlarmS1 Hysteresis 9.000mS/cm 0.0µS/cm +inf
AlarmS1 DelayTime 0.2sec. 0.0sec. +inf
AlarmS1 ExpireTime 0.0sec. 0.0sec. 1800sec.
AlarmS2 Setpoint 100.0mS/cm(low) -inf +inf
AlarmS2 Hysteresis 1.000mS/cm 0.0µS/cm +inf
AlarmS2 DelayTime 0.2sec. 0.0sec. +inf
AlarmS2 ExpireTime 0.0sec. 0.0sec. 1800sec.
S1(control) ExpireTime 0.0sec. 0.0sec. 1800sec.
P-controlS1 Setpoint 500.0mS/cm -inf +inf
P-controlS1 Range 100.0mS/cm -inf +inf
P-controlS1 ManualReset 0.000% 0% 100%
PID-controlS1 I-time 3600sec. 1.0sec. 3600sec.
PID-controlS1 D-time 0.0sec. 0.0sec. 60sec.
S2,S3,S4SimilarstructuretoS1