IM 5E1E70-01E
10
7. KEY OPERATIONS
NOTE
At power-on, the controller displays the operation display , but if the input range setting remains OFF,
then “IN” appears. In this case, press the key to display the input range code you want to use, then
press the key to register it. (Refer to the flowchart on page 12 and 13.)
(1) You can move between parameter setting displays using the key.
(2) To change the set value,
(i) Change the display value with the or key
(the period flashes).
(ii) Press the key to register the setting.
(3) At the operation display , or , pressing the key for at least 3
seconds retrieves the operation parameter setting display.
(4) At the operation parameter setting display, pressing the key for at
least 3 seconds transfers back to the operation display . Registering the
key-lock parameter LOC to “–1” retrieves the setup parameter setting
display.
(5) At the setup parameter setting display, pressing the key for at least
3 seconds transfers back to the operation display . Registering the
parameter PRG to “–1” retrieves the program parameter setting display.
(6) At the program parameter setting display, pressing the key for at
least 3 seconds transfers back to the operation display .
When “In” appears, press the
key to display the input range code
you want to use, then press the
key to register it. After this
operation, the controller shows the
operation display
.
NOTE
Note: If you cannot change,
check the key-lock
parameter (LOC) setting.
1
2
3
4
5
8
10
14
15
16
17
31
32
33
34
35
38
40
44
45
46
47
Thermocouple
RTD
K
J
R
B
Platinel 2
Pt100
270 to 1370°C
0.0 to 600.0°C
0.0 to 400.0°C
199.9 to 200.0°C
199.9 to 999.9°C
0 to 1700°C
0 to 1800°C
0 to 1390°C
199.9 to 850.0°C
0.0 to 400.0°C
199.9 to 200.0°C
300 to 2500°F
32.0 to 999.9°F
32.0 to 750.0°F
300 to 400°F
300 to 2100°F
32 to 3100°F
32 to 3200°F
32 to 2500°F
199.9 to 999.9°F
32.0 to 750.0°F
300 to 400°F
For example, to select
thermocouple type J (°F),
set the range code to 35.
UT150 Input Ranges
Input type Range
(
°C
)
Range
(
°F
)
Range code
(
°C
)
Range code
(
°F
)

Other manuals for YOKOGAWA UP150

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YOKOGAWA UP150 and is the answer not in the manual?

YOKOGAWA UP150 Specifications

General IconGeneral
BrandYOKOGAWA
ModelUP150
CategoryTemperature Controller
LanguageEnglish

Related product manuals