5292157-UIM-B-0317
Johnson Controls Unitary Products 19
AVV61D
6HK(0,1)6500206 10
19.9 20.7 25 25
6HK(0,1)6500506 20
30.8 32.7 35 35
6HK(0,1)6500806 32
44.0 47.3 45 50
6HK(0,1)6501006 40
52.4 56.6 60 60
6HK(1,2)6501306 52
65.6 71.3 70 80
6HK(1,2)6501506 60
74.0 80.5 80 90
6HK(1,2)6501806 72
87.3 95.2 90 100
6HK(1,2)6502006 80
95.7 104.4 100 110
6HK(1,2)6502506 100
117.3 128.3 125 150
NOTES:
1. (0,1) - maybe 0 (no service disconnect) or 1 (with service disconnect).
2. (1,2) maybe 1 (with service disconnect, no breaker jumper bar) or 2 (with service disconnect & breaker jumper bar).
3. MOP = Maximum Overcurrent Protection device; must be HACR type circuit breaker or time delay fuse. Refer to the latest edition of the National Electric Code or
in Canada the Canadian electrical Code and local codes to determine correct wire sizing.
TABLE 10:
Electrical Data For Single Source Power Supply: 208/230-1-60 (Continued)
Air Handler Models
Heater Models
1,2
Heater Amps @240V
Field Wiring
Min. Circuit Ampacity
MOP
3
208V 230V 208V 230V