TABLE 13:
Electrical Data For Multi-source Power Supply: 208/230-3-60
Air Handlers
Models
Heater
Models
1
Heater Amps
@240V
Min. Circuit Ampacity
MOP
2
208V 230V 208V 230V
Circuit Circuit
1st
2
2nd
1st
2
2nd
1st
2
2nd
1st
2
2nd
25B 6HK46502025 46.2 31.3 25.0 33.3 27.6 35 25 35 30
37B 6HK46502025 46.2 28.8 22.6 30.6 25.0 35 25 35 30
37C 6HK46502025 46.2 31.3 25.0 33.3 27.6 35 25 35 30
38B TBD TBD TBD TBD TBD TBD TBD TBD TBD TBD
38C 6HK46502025 46.2 31.3 25.0 33.3 27.6 35 25 35 30
49C 6HK46502025 46.2 34.1 25.0 36.4 27.6 35 25 40 30
49D
6HK46502025 46.2 34.1 25.0 36.4 27.6 35 25 40 30
6HK46502525 57.7 40.4 31.3 43.3 34.6 45 35 45 35
50C
6HK46502025 46.2 9.1 0.0 8.8 0.0 35 25 40 30
6HK46502525 57.7 9.1 0.0 8.8 0.0 45 35 45 35
50D
6HK46502025 46.2 27.9 18.8 29.5 20.7 35 25 40 30
6HK46502525 57.7 31.7 22.6 33.7 25.0 45 35 45 35
61C 6HK46502025 46.2 34.1 25.0 36.4 27.6 35 25 40 30
61D
6HK46502025 46.2 34.1 25.0 36.4 27.6 35 25 40 30
6HK46502525 57.7 40.4 31.3 43.3 34.6 45 35 45 35
NOTES:
1. The 20kW and 25kW heater models (6HK46502025 and 6HK46502525) come with service disconnects standard.
2. MOP = Maximum Overcurrent Protection device; must be HACR type circuit breaker or time delay fuse. The 1st circuit includes blower motor amps. Refer to the
latest edition of the National Electric Code or in Canada the Canadian electrical Code and local codes to determine correct wire sizing.
TABLE 14: Air Flow Data (CFM)
1, 2, 3, 4
(When operating with electric heat section.)
High/Low Speed Heat CFM
Heat Tap2
AVV25B AVV37B AVV37C AVV38B AVV38C AVV49C
High Low High Low High Low High Low High Low High Low
A 1225 1020 1225 1020 1425 1150 TBD TBD 1430 1200 1650 1200
B 1150 950 1150 950 1150 1000 TBD TBD 1375 1150 1550 1150
C 950 750 950 750 925 925 TBD TBD 1150 1050 1375 1050
D 725 725 725 725 675 675 TBD TBD 900 900 1150 1000
Heat Tap
AVV49D AVV50C AVV50D AVV61C AVV61D
High Low
High Low High Low High Low High Low
A 1650 1150 1650 1200 1650 1150 1850 1250 1825 1150
B 1600 1050 1550 1150 1600 1050 1775 1200 1775 1050
C 1325 1000 1375 1050 1325 1000 1570 1150- 1570 1000
D 1125 780 1150 1000 1125 780 1370 1050 1375 950
NOTES:
1. Air handler units have been tested to UL 1995 / CSA 22.2 No. 236 standards up to 0.50" wc. external static pressure.
Dry coil conditions only, tested without filters.
For optimal performance, external static pressures of 0.2" to 0.5" are recommended. Heating applications tested at 0.50” w.c. esp. Above 0.5" CFM is reduced by
2% per 0.1" increase in static.
2. The ADJ tap does not affect the HEAT tap setting.
Airflow (CFM) indicator light (LED2) flashes once for every 100 CFM (i.e.: 12 flashes is 1200 CFM) - blinks are approximate +/- 10% of actual CFM.
3. All CFM are shown at 0.5" w.c. external static pressure. These units have variable-speed ECM motors that automatically adjust to provide constant CFM from 0.0"
to 0.4" WC. external static pressure. From 0.4" to 0.8" external static pressure, CFM is reduced by 2% per 0.1" static pressure. Operation of these units on duct sys-
tems with external static pressure greater than 0.8" is not recommended.
4. Airflow may be lower than what is required to operate an airflow switch on certain models of electronic air cleaners. Consult the instructions for the electronic air
cleaner for further details.