5292157-UIM-B-0317
20 Johnson Controls Unitary Products
TABLE 11:
Electrical Data For Multi-source Power Supply: 208/230-1-60
Air Handlers Models
Heater Models
1,2
Heater Amps @240V
Min. Circuit Ampacity
MOP
3
208V 230V 208V 230V
Circuit Circuit
1st
3
2nd 3rd
1st
3
2nd 3rd
1st
3
2nd 3rd
1st
3
2nd 3rd
25B
6HK16501306 52 25.0 37.6 – 26.4 41.5 – 25 40 – 30 45 –
6HK16501506 60 27.9 43.3 – 29.6 47.9 – 30 45 – 30 50 –
6HK16501806 72 45.3 39.0 – 48.8 43.1 – 50 40 – 50 45 –
6HK16502006 80 49.6 43.3 – 53.5 47.9 – 50 45 – 60 50 –
37B
6HK16501306 52 25.0 37.6 – 26.4 41.5 – 25 40 – 30 45 –
6HK16501506 60 27.9 43.3 – 29.6 47.9 – 30 45 – 30 50 –
6HK16501806 72 45.3 39.0 – 48.8 43.1 – 50 40 – 50 45 –
6HK16502006 80 49.6 43.3 – 53.5 47.9 – 50 45 – 60 50 –
37C
6HK16501306 52 25.0 37.6 – 26.4 41.5 – 25 40 – 30 45 –
6HK16501506 60 27.9 43.3 – 29.6 47.9 – 30 45 – 30 50 –
6HK16501806 72 45.3 39.0 – 48.8 43.1 – 50 40 – 50 45 –
6HK16502006 80 49.6 43.3 – 53.5 47.9 – 50 45 – 60 50 –
38B TBD TBD TBD TBD TBD TBD TBD TBD TBD TBD TBD TBD TBD TBD
38C
6HK16501306 52 25.0 37.6 – 26.4 41.5 – 25 40 – 30 45 –
6HK16501506 60 27.9 43.3 – 29.6 47.9 – 30 45 – 30 50 –
6HK16501806 72 45.3 39.0 – 48.8 43.1 – 50 40 – 50 45 –
6HK16502006 80 49.6 43.3 – 53.5 47.9 – 50 45 – 60 50 –
49C
6HK16501306 52 27.9 37.6 – 29.5 41.5 – 30 40 – 30 45 –
6HK16501506 60 30.8 43.3 – 32.7 47.9 – 35 45 – 35 50 –
6HK16501806 72 48.1 39.0 – 51.9 43.1 – 50 40 – 60 45 –
6HK16502006 80 52.5 43.3 – 56.7 47.9 – 60 45 – 60 50 –
49D
6HK16501306 52 27.9 37.6 – 29.5 41.5 – 30 40 – 30 45 –
6HK16501506 60 30.8 43.3 – 32.7 47.9 – 35 45 – 35 50 –
6HK16501806 72 48.1 39.0 – 51.9 43.1 – 50 40 – 60 45 –
6HK16502006 80 52.5 43.3 – 56.7 47.9 – 60 45 – 60 50 –
6HK16502506 100 52.5 43.3 21.7 56.7 47.9 24.0 60 45 25 60 50 25
50C
6HK16501306 52 27.9 37.6 – 29.5 41.5 – 30 40 – 30 45 –
6HK16501506 60 30.8 43.3 – 32.7 47.9 – 35 45 – 35 50 –
6HK16501806 72 48.1 39.0 – 51.9 43.1 – 50 40 – 60 45 –
6HK16502006 80 52.5 43.3 – 56.7 47.9 – 60 45 – 60 50 –
50D
6HK16501306 52 27.9 37.6 – 29.5 41.5 – 30 40 – 30 45 –
6HK16501506 60 30.8 43.3 – 32.7 47.9 – 35 45 – 35 50 –
6HK16501806 72 48.1 39.0 – 51.9 43.1 – 50 40 – 60 45 –
6HK16502006 80 52.5 43.3 – 56.7 47.9 – 60 45 – 60 50 –
6HK16502506 100 52.5 43.3 21.7 56.7 47.9 24.0 60 45 25 60 50 25
61C
6HK16501306 52 27.9 37.6 – 29.5 41.5 – 30 40 – 30 45 –
6HK16501506 60 30.8 43.3 – 32.7 47.9 – 35 45 – 35 50 –
6HK16501806 72 48.1 39.0 – 51.9 43.1 – 50 40 – 60 45 –
6HK16502006 80 52.5 43.3 – 56.7 47.9 – 60 45 – 60 50 –
61D
6HK16501306 52 27.9 37.6 – 29.5 41.5 – 30 40 – 30 45 –
6HK16501506 60 30.8 43.3 – 32.7 47.9 – 35 45 – 35 50 –
6HK16501806 72 48.1 39.0 – 51.9 43.1 – 50 40 – 60 45 –
6HK16502006 80 52.5 43.3 – 56.7 47.9 – 60 45 – 60 50 –
6HK16502506 100 52.5 43.3 21.7 56.7 47.9 24.0 60 45 25 60 50 25
NOTES:
1. (0,1) - maybe 0 (no service disconnect) or 1 (with service disconnect).
2. (1,2) maybe 1 (with service disconnect, no breaker jumper bar) or 2 (with service disconnect & breaker jumper bar).
3. MOP = Maximum Overcurrent Protection device; must be HACR type circuit breaker or time delay fuse. Refer to the latest edition of the National Electric Code or
in Canada the Canadian electrical Code and local codes to determine correct wire sizing.