EasyManua.ls Logo

York DM090 - Additional Static Resistance 50 Cabinet; Additional Static Resistance 42 Cabinet

York DM090
60 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
127408-YIM-B-0606
Unitary Products Group 37
TABLE 39: ADDITIONAL STATIC RESISTANCE 50” CABINET (IMPERIAL)
CFM
Cooling Only
*
Economizer
Electric Heat KW
9 18243654
1900 0.06 0.02 0.05 0.06 0.07 0.08 0.10
2100 0.07 0.02 0.06 0.07 0.08 0.09 0.11
2300 0.08 0.02 0.07 0.08 0.09 0.10 0.13
2500 0.09 0.02 0.08 0.09 0.10 0.11 0.14
2700 0.11 0.03 0.09 0.10 0.12 0.13 0.16
2900 0.12 0.03 0.10 0.11 0.13 0.14 0.18
3100 0.14 0.03 0.12 0.13 0.15 0.16 0.20
3300 0.16 0.03 0.13 0.14 0.17 0.18 0.22
3500 0.18 0.04 0.15 0.16 0.19 0.20 0.24
3700 0.20 0.04 0.17 0.18 0.21 0.22 0.26
3900 0.23 0.04 0.19 0.20 0.23 0.24 0.28
4100 0.25 0.04 0.21 0.22 0.25 0.26 0.31
4300 0.28 0.05 0.23 0.24 0.28 0.29 0.34
4500 0.30 0.05 0.25 0.26 0.30 0.31 0.37
4700 0.33 0.05 0.28 0.29 0.33 0.34 0.40
4900 0.36 0.05 0.30 0.31 0.35 0.37 0.43
5100 0.39 0.06 0.33 0.34 0.38 0.40 0.46
5300 0.42 0.06 0.35 0.37 0.41 0.43 0.49
5500 0.45 0.06 0.38 0.40 0.44 0.46 0.53
5700 0.48 0.06 0.41 0.43 0.47 0.49 0.56
5900 0.52 0.07 0.44 0.46 0.50 0.53 0.59
6100 0.56 0.07 0.47 0.49 0.53 0.56 0.62
6300 0.60 0.07 0.50 0.53 0.56 0.59 0.65
*.
Add these resistance values to the available static resistance in the respective Blower Performance Tables.
†.
Deduct these resistance values from the available external static pressure shown in the respective Blower Performance Table.
‡.
The pressure drop through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return
air duct system is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.
TABLE 40: ADDITIONAL STATIC RESISTANCE 42” CABINET (IMPERIAL)
CFM
Cooling Only
*
Economizer
1900 -0.004 0.07
2100 0.01 0.09
2300 0.01 0.11
2500 0.02 0.13
2700 0.03 0.16
2900 0.04 0.18
3100 0.05 0.20
3300 0.06 0.22
3500 0.07 0.24
3700 0.08 0.27
3900 0.09 0.29
4100 0.09 0.31
4300 0.10 0.33
*.
Add these resistance values to the available static resistance in the respective Blower Performance Tables.
†.
Deduct these resistance values from the available external static pressure shown in the respective Blower Performance Table.
‡.
The pressure drop through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return
air duct system is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.

Table of Contents

Related product manuals