036-21342-002 Rev. E (0505)
Unitary Products Group 3
Physical and Electrical Data
MODEL
E4TS030 E4TS036 E4TS048 E4TS060
UNIT SUPPLY VOLTAGE 208/230-1-60
NORMAL VOLTAGE RANGE
1
1. Rated in accordance with ARI Standard 110, utilizaton range “A”.
187 to 252
MIN. CIRCUIT AMPACITY 14.8 18.3 28.0 34.4
MAX. OVERCURRENT DEVICE AMPS
2
2. Dual element fuses or HACR circuit breaker.
25 30 50 60
COMPRESSOR TYPE T27B264CBCA T27B355CBCA T29A464BBCA T29A544BBCA
COMPRESSOR AMPS
RATED LOAD 11.3 14.1 21.2 26.3
LOCKED ROTOR 65 84 130 142
CRANKCASE HEATER YES YES YES YES
FAN MOTOR AMPS RATED LOAD .7 .7 1.5 1.5
FAN DIAMETER INCHES 24 24 24 24
FAN MOTOR
RATED HP 1/10 1/10 1/4 1/4
NOMINAL RPM 825 825 825 850
NOMINAL CFM 2650 2650 3200 3200
COIL
FACE AREA SQ. FT.20.020.020.020.0
ROWS DEEP1122
FIN / INCH 16 16 13 13
LIQUID LINE OD 3/8 3/8 3/8 3/8
VAPOR LINE OD 7/8 7/8 7/8 7/8
UNIT CHARGE, (LBS - OZ)
3
3. The Unit Charge is correct for the outdoor unit, matched indoor coil and 15 feet of refrigerant tubing. For tubing lengths other than
15 feet, add or subtract the amount of refrigerant calculated, using the difference in length multiplied by the per foot value.
9 - 9 10 - 1 12 - 1 13 - 1
CHARGE PER FOOT, OZ .70 .70 .70 .70
OPERATING WEIGHT LBS. 242 242 310 310
All dimensions are in inches. They are subject to change without
notice. Certified dimensions will be provided upon request.
48" OVERHEAD
CLEARANCE
C
B
A
5-1/2
2-3/8
3-1/8
VAPOR
CONNECTION
LIQUID CONNECTION
AIR IN
4 SIDES
UNIT
MODEL
E4TS
DIMENSIONS
REFRIGERANT
CONNECTION
LINE SIZE
ABC
LIQUID VAPOR
030
31-7/8 35 35
3/8
7/8
036
31-7/8 35 35
048
31-7/8 35 35
060
37-7/8 35 35