036-21371-001-B-0203
10 Unitary Products Group
TABLE 8: SUPPLY AIR PLENUM PERFORMANCE DATA
INDOOR
UNIT
MODEL
FA
CFM
FACE
VELO
CITY
(FPM)
ANGLE OF DEFLECTION
VERTICAL
LOUVERS
1
(PLAN
VIEW)
HORIZONTAL
LOUVERS
2
(ELEVATION
VIEW)
VERTICAL
LOUVERS
1
(PLAN
VIEW)
HORIZON-
TAL
LOUVERS
2
(ELEVATION
VIEW)
VERTICAL
LOUVERS
1
(PLAN
VIEW)
HORIZONTAL
LOUVERS
2
(ELEVATION
VIEW)
THROW
(FEET
3
)
SPREAD
(FEET)
3
THROW
(FEET)
3
SPREAD
(FEET)
3
THROW
(FEET)
3
SPREAD
(FEET)
3
MIN. MAX. MIN. MAX
DROP (FEET)
4
MIN. MAX MIN. MAX
DROP (FEET)
4
MIN. MAX. MIN. MAX.
DROP (FEET)
4
090
2400 615 47 74 20 29 19 9 34 53 23 33 17 8 26 39 45 65 9 5
2700 690 53 83 22 32 20 10 39 59 25 36 18 9 29 45 48 71 10 5
3000 770 59 92 24 35 21 10 42 66 27 40 19 9 32 50 52 78 10 5
3300 845 65 101 26 38 21 10 46 73 29 44 19 9 35 55 56 85 10 5
3600 920 71 110 28 41 22 11 50 79 32 47 20 10 38 60 60 91 11 6
1
Adjusting the vertical louvers will vary the throw, the spread and the drop.
2
Adjusting the horizontal louvers will only vary the drop.
3
The velocity of the air will be 125 ft./min. at the minimum distance and 80 ft./min. at the maximum distance.
4
The velocity of the conditioned air at the bottom of the drop will be 50 ft./min. Drafts will occur if the drop extends into the occu-
pied level of the conditioned space.
0 °
S P R E A D
2 2 - 1 / 2 °
S P R E A D
4 5 °
S P R E A D
0 °
S P R E A D
18˚
0 °
S P R E A D
18˚
0 °
S P R E A D
18˚
FIGURE 3: FA090 AIRFLOW CHART
7
.5-ton Heat Pump
2400
2600
2800
3000
3200
3400
3600
3800
4000
4200
4400
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 1.1
Static
CFM
O turns
1 turn
2 turns
3 turns
4 turns
5 turns