036-21371-001-B-0203
Unitary Products Group 17
To determine the total circuit length, add the following distances:
1 - Outdoor Unit to Indoor Unit ________
2 - Indoor Unit to Thermostat ________
3 - Thermostat to Indoor Unit ________
4 = Indoor Unit to Outdoor Unit ________
Total Circuit Length ________
TABLE 12: PHYSICAL DATA - ELECTRIC HEAT ACCESSORIES
Description
Nominal Heater Capacity
10 kW 16 KW 26 KW 36 KW
Heater Elements
% Nickel 59.2
% Chromium 16.0
Coil ID - inches 9/32
Watt Density - watts/sq.in. 59
Rows Deep 1 2 3 4
Face Area - square feet 3.0
TABLE 13: ELECTRICAL DATA - OUTDOOR UNIT
Model
EFB
Compressor Outdoor Fan Motor
Min.
Circuit
Amps
Max.
Fuse
Size
Min. Wire
Size,
1
AWG
Power
Supply
RLA LRA
Power
Factor
Power
Supply
Qty.
FLA
(Each)
090A
25 200/230-3-60 25.6 190.0
0.94 @ 208V
208/230-1-60 2 3.03 38.1 60 8
0.84 @ 230V
46 460-3-60 12.8 95.0 0.86 460-1-60 2 1.6 19.2 30 10
1
Based on three, 60ºC insulated copper conductors in steel conduit.
TABLE 14: INDOOR UNIT - HEAT PUMP ONLY
Blower
Motor
HP
Power
Supply
FLA
Max. Fuse
Size,
1
AMPS
1
Dual element, time delay fuses.
FA090
1-1/2
208-3-60 5.2 15
230-3-60 5.0 15
460-3-60 2.6 15
TABLE 15: CONTROL WIRE SIZING
Wire Size
Max. Total
Circuit Length, (Ft.)
#19 Solid 130
#18 Solid 170
#18 Stranded 180
#16 Stranded 270
#14 Stranded 455
#12 Stranded 730