York EA090 - ARI Ratings; System Application Data; Refrigerant Piping Limitations

York EA090
20 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
036-21371-001-B-0203
4 Unitary Products Group
1
Certified in accordance with the Unitary Large Equipment certification program, which is based on ARI Standard 340/360.
2
Rated in accordance with ARI Standard 270.
3
Deduct 1 MBH when a unit operates at 208 volts.
TABLE 1: ARI RATINGS
1
- COOLING, HEATING AND SOUND
Model Cooling Capacity
Heating Capacity
High Outdoor
Temperature (47º F)
Low Outdoor
Temperature (17º F)
Outdoor
Unit
Indoor
Unit
MBH
3
EER
MBH
3
COP
MBH
3
COP
EA090 FA090
90 10.67 87.7 3.25 55 2.34
Outdoor Unit
Sound Rating
2
(bels)
EA090 8.9
TABLE 2: SYSTEM APPLICATION DATA
Air Temperature on OUTDOOR Coil, ºF Air Temperature on INDOOR Coil, ºF
Minimum Maximum minimum Maximum
Cool Heat Cool heat Cool Heat Cool Heat
40 db
0 db
1
115 db 75 db 57 wb
50 db
2
72 wb 80 db
1
Below 0ºF, the control circuit will lock out the compressor and allow the electric heat
accessory to cycle at its standby capacity.
Air Flow across INDOOR Coil, CFM (Min./Max.)
2
Operation below this temperature is permissible for a short period of time when a
unit is required to heat the conditioned space up to 50ºF.
FA090 2400/3600
TABLE 3: REFRIGERANT PIPING LIMITATIONS
1
System
(Tons)
Maximum
Vertical Rise,
2
(Feet)
Maximum
Total Length
(Feet)
7-1/2 60 125
1
Refer to installation instruction Form 035-18474-000 for more
detailed information on refrigerant piping.
2
Based on the loss of static head in the liquid riser during the
heating cycle.