036-21024-006 Rev. D (0403)
Unitary Products Group 19
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree belowthe listed temperature.
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO. H4DB076
INDOOR COIL MODEL NO. KEU090A33A
CONDENSER
ENTERING AIR
TEMPERATURE
ID CFM 1900 2550 3150
ID DB (°F) 85 80 70 85 80 70 85 80 70
ID WB (°F) 72 67 57 72 67 57 72 67 57
75
T.C. 75.4 72.8 70.5 78.2 75.5 73.4 81.0 78.2 76.2
S.C. 46.5 46.3 45.9 52.8 52.7 52.2 59.1 59.0 58.4
K.W 6.11 6.03 5.97 6.42 6.32 6.29 6.72 6.62 6.60
85
T.C. 72.9 70.3 67.3 75.4 72.8 70.0 77.9 75.3 72.7
S.C. 45.7 45.4 44.6 52.2 51.9 51.1 58.6 58.3 57.5
K.W 6.67 6.56 6.51 7.01 6.89 6.85 7.34 7.22 7.19
95
T.C. 70.4 67.8 64.1 72.6 70.1 66.7 74.8 72.4 69.2
S.C. 44.9 44.5 43.3 51.5 51.1 50.0 58.1 57.6 56.6
K.W 7.23 7.09 7.05 7.60 7.46 7.42 7.96 7.82 7.78
105
T.C. 67.8 64.3 59.7 69.7 66.5 62.2 71.6 68.7 64.6
S.C. 44.2 43.3 41.7 50.6 49.8 48.1 57.0 56.2 54.5
K.W 8.01 7.87 7.78 8.39 8.26 8.16 8.76 8.65 8.54
115
T.C. 65.2 60.8 55.3 66.8 63.9 57.7 68.4 65.0 60.0
S.C. 43.3 42.0 40.0 49.6 49.5 46.2 55.9 54.8 52.4
K.W 8.78 8.64 8.50 9.17 8.99 8.90 9.56 9.48 9.30
125
T.C. 62.6 57.3 50.9 63.9 61.3 53.2 65.2 61.3 55.4
S.C. 42.4 40.7 38.3 48.6 49.2 44.3 54.8 53.4 50.3
K.W 9.55 9.41 9.22 9.96 9.72 9.64 10.36 10.31 10.06
NOTE:
NOTE: ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.