036-21023-002 Rev. A (5/00)
Unitary Products Group 15
ACCESSORIES (Refer to Price Manual for specific model numbers.)
Dehumidification Control - Model 2HU06700124 available for use
in areas where a higher level of humidity control is required.
Room Thermostat - Matching 2-Stage cooling thermostats are avail-
able to provide features required for any installation. See list below:
2ET03700024 2ET03700124
2ET03700224 2ET03700324
TXV Kit - Factory specified and required for proper unit performance.
H4TS024 = 1TV0701
H4TS030 = 1TV0701
H4TS036 = 1TV0702
H4TS048 = 1TV0704 (w/ 4 ton evap coils)
1TV0703 (w/ 5 ton evap coils)
H4TS060 = 1TV0703
Table 6:
PHYSICAL AND ELECTRICAL DATA
MODEL H4TS024 H4TS030 H4TS036 H4TS048 H4TS060
UNIT SUPPLY VOLTAGE 208/230-1-60
NORMAL VOLTAGE RANGE
1
187 to 252
MIN. CIRCUIT AMPACITY 13.4 15.3 18.6 32.8 35.3
MAX. OVERCURRENT DEVICE AMPS
2
20 25 30 50 60
COMPRESSOR TYPE BRISTOL TS
COMPRESSOR AMPS
RATED LOAD 10.3 11.7 13.5 25.7 27.0
LOCKED ROTOR 64 65 84 135 147
CRANKCASE HEATER YES YES YES YES YES
FAN MOTOR AMPS RATED LOAD .5 .5 .7 .7 1.5
FAN DIAMETER INCHES 18 18 24 24 24
FAN MOTOR
RATED HP 1/12 1/12 1/10 1/10 1/4
NOMINAL RPM 1100 1100 825 825 850
NOMINAL CFM 1850 1850 2800 2800 3200
COIL
FACE AREA SQ. FT 14.2 14.2 20.0 24.0 24.0
COIL ROWS DEEP 1 1 1 1 1
FIN / INCH 20 20 20 20 20
LIQUID LINE OD 3/8 3/8 3/8 3/8 3/8
VAPOR LINE OD 3/4 3/4 7/8 7/8 7/8
UNIT CHARGE, (LBS - OZ)
3
5 - 9 6 - 9 7 - 0 9 - 12 9 - 2
CHARGE PER FOOT, OZ .68 .68 .70 .7 .7
OPERATING WEIGHT LBS. 145 145 200 250 252
1
Rated in accordance with ARI Standard 110. utilization range “A”.
2
Dual element fuses or HACR circuit breaker.
3
The Unit Charge is correct for the outdoor unit, matched indoor coil and 15 feet of refrigerant tubing. For tubing lengths other
than 15 feet, add or subtract the amount of refrigerant calculated, using the difference in length multiplied by the per foot value.
UNIT
MODEL
HTS
DIMENSIONS
REFRIGERANT
CONNECTION
LINE SIZE
ABCLIQUIDVAPOR
024 30-1/8 24 24
3/8
3/4
030 30-1/8 24 24
036 31-7/8 35 35
7/8048 37-7/8 35 35
060 37-7/8 35 35
48" OVERHEAD
CLEARANCE
C
B
A
5-1/2
2-3/8
3-1/8
VAPOR
CONNECTION
LIQUID CONNECTION
AIR IN
4 SIDES