036-21345-001-B-0105
Unitary Products Group 3
FEATURES
• Copeland Scroll compressors provide both high effi-
ciency and reliability.
• Condenser coils are constructed of copper tubes and
aluminum fins for durability and long lasting efficient
operation.
• Crankcase heaters that will be de-energized when the
compressor is operating.
• Both high and low pressure controls. Since these con-
trols are self-contained, there are no capillary lines to be
damaged.
• Solid state or internal line break compressor motor pro-
tection.
• Class 2, 24-volt thermostat control circuit.
• A sight glass and filter-drier is shipped in the unit's con-
trol box for field installation in the liquid line near the
evaporator coil. Two are provided on all 30, 40 and 50
ton models.
• Copper stub-outs are factory mounted on the suction
and liquid lines to simplify the field piping connections.
• Multiple controls to provide stable system operation at
ambient temperatures down to 40ºF.
• Capacity reduction for more economical operation and
more even temperature levels within the conditioned
space.
• A lockout circuit to prevent the unit from cycling on safety
control.
• Pumpout on unit startup to prevent allowing liquid refrig-
erant returning to the compressor.
*Rated in accordance with ARI Standard 360 (60 Hz).
EER = Energy Efficiency Ratio at full load - the cooling capacity in Btu’s
per hour (Btuh) divided by the power input in watts, expressed in Btuh per
watt (Btuh/watt).
TABLE 1: RATINGS*
Condensing
Unit
Evaporator
Blower Unit
Capacity,
MBH
EER
HA300 LA300 320 10.0
HB360 LB360 376 9.5
HB480 LB480 485 8.8
HB480 LB600 510 9.7
HB600 LB600 600 9.5
TABLE 2: UNIT APPLICATION DATA
Voltage Variation
1
Min./Max.
1
Utilization range “A” in accordance with ARI Standard 110.
380/415V-3-50 342/456
Ambient Air on Condenser Coil
Min./Max.
40°F/125°F
2
2
These units can operate in an ambient temperature of 125°F pro-
viding the wet bulb temperature of the air entering the evaporator
coil does not exceed 67°F.