York HB360 - Product Features; Compressor and Coil Features

York HB360
24 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
036-21345-001-B-0105
Unitary Products Group 3
FEATURES
Copeland Scroll compressors provide both high effi-
ciency and reliability.
Condenser coils are constructed of copper tubes and
aluminum fins for durability and long lasting efficient
operation.
Crankcase heaters that will be de-energized when the
compressor is operating.
Both high and low pressure controls. Since these con-
trols are self-contained, there are no capillary lines to be
damaged.
Solid state or internal line break compressor motor pro-
tection.
Class 2, 24-volt thermostat control circuit.
A sight glass and filter-drier is shipped in the unit's con-
trol box for field installation in the liquid line near the
evaporator coil. Two are provided on all 30, 40 and 50
ton models.
Copper stub-outs are factory mounted on the suction
and liquid lines to simplify the field piping connections.
Multiple controls to provide stable system operation at
ambient temperatures down to 40ºF.
Capacity reduction for more economical operation and
more even temperature levels within the conditioned
space.
A lockout circuit to prevent the unit from cycling on safety
control.
Pumpout on unit startup to prevent allowing liquid refrig-
erant returning to the compressor.
*Rated in accordance with ARI Standard 360 (60 Hz).
EER = Energy Efficiency Ratio at full load - the cooling capacity in Btu’s
per hour (Btuh) divided by the power input in watts, expressed in Btuh per
watt (Btuh/watt).
TABLE 1: RATINGS*
Condensing
Unit
Evaporator
Blower Unit
Capacity,
MBH
EER
HA300 LA300 320 10.0
HB360 LB360 376 9.5
HB480 LB480 485 8.8
HB480 LB600 510 9.7
HB600 LB600 600 9.5
TABLE 2: UNIT APPLICATION DATA
Voltage Variation
1
Min./Max.
1
Utilization range “A” in accordance with ARI Standard 110.
380/415V-3-50 342/456
Ambient Air on Condenser Coil
Min./Max.
40°F/125°F
2
2
These units can operate in an ambient temperature of 125°F pro-
viding the wet bulb temperature of the air entering the evaporator
coil does not exceed 67°F.